44
System Start-Up
Table 8A
Chilled Solution Reset Schedule based on Zone Temperature
Active Leaving
Solution Setpoint
Reset
Amount = Maximum
LSS = ALSS + Maximum
Reset
Amount = Zero (0)
LSS = ALSS
Adjustable
Reset
3 - 16 F
End Temperature
Range 66 - 81
Factory Preset = 75
Start Temperature
Range 66 - 81
Factory Preset = 78
Zone
Temperature
Zone Reset Cooling
Factory
Preset = 5
Table 8B
Chilled Solution Reset Schedule based on Outside Air Temperature
Active Leaving
Solution Setpoint
Reset
Amount = Maximum
LSS = ALSS + Maximum
Reset
Amount = Zero (0)
LSS = ALSS
Adjustable
Reset
3 - 16 F
End Temperature
Range 65 - 125
Factory Preset = 70
Start Temperature
Range 65 - 125
Factory Preset = 90
OA
Temperature
Outside Air Reset Cooling
Factory
Preset = 5
Содержание IntelliPak CG-SVX02B-EN
Страница 10: ...10 General Information Module Mounting Locations Screw Hole...
Страница 12: ...12 Figure 1 Typical Installation Clearances for Single Multiple or Pit Applications...
Страница 13: ...13 Figure 2 C20 Ton Unit Dimensional Data Recommended Clearances...
Страница 14: ...14 Figure 2 C25 Ton Unit Dimensional Data Recommended Clearances...
Страница 15: ...15 Figure 2 C30 Ton Unit Dimensional Data Recommended Clearances...
Страница 16: ...16 Figure 2 C40 Ton Unit Dimensional Data Recommended Clearances...
Страница 17: ...17 Figure 2 C50 Ton Unit Dimensional Data Recommended Clearances...
Страница 18: ...18 Figure 2 C60 Ton Unit Dimensional Data Recommended Clearances...
Страница 35: ...35...
Страница 36: ...36 Figure 12B Typical GBAS 0 5 Volt Connections Diagram...
Страница 37: ...37...
Страница 38: ...38...
Страница 63: ...63...
Страница 64: ......