5.4 Safety-oriented function inputs
In order to comply with the specified data, only cables with a maximum length of
10 m may be used to connect the safe function inputs.
IN11, IN12, IN21
Non-destructive voltage range ...................................
≤ 35 V DC
Input impedance ......................................................... 4.8 kOhm
Low level ....................................................................
0…4 VDC
High level ....................................................................
18…35 VDC
Galvanic isolation ....................................................... no
Pulse suppression time ..............................................
(for test pulses of an OSSD signal)
0.15 ms
5.5 Message outputs
●
Risk of damage to the message outputs due to excessively high cur-
rent flow!
Current-limiting measures must be implemented to ensure that the cur-
rent flow does not exceed 50 mA.
C1 = safe state, C2 = error
Output voltage ............................................................ 24 VDC
Output current ............................................................
≤ 50 mA
Galvanic isolation ....................................................... no
Short-circuit resistance ............................................... no
Galvanic isolation ....................................................... no
Output voltage at full load .......................................... Supply
–1V