Parameterization via TRWinProg
TR-Electronic GmbH 2011, All Rights Reserved
Printed in the Federal Republic of Germany
Page 48 of 55
TR - ECE - BA - DGB - 0084 - 05
06/28/2017
4.1.3 Preset value
Specification of the position value, on which the measuring system is adjusted when
the preset-adjustment-function is executed via the Preset-input.
programmed
Origin Type
≤
Preset value
< programmed
Total number of steps
CE_-65
CO_-65
lower limit
-1073741824 steps
-33554432000 steps
upper limit
1073741824 steps
33554432000 steps
default
0
0
4.1.4 Preset function
Risk of injury and damage to property by an actual value jump when the
Preset adjustment function is performed!
•
The preset adjustment function should only be performed when the
measuring system is at rest, otherwise the resulting actual value jump must
be permitted in the program and application!
If the Preset inputs are not used, they should be disabled to suppress interference.
Selection
Description
Default
In use
Preset adjustment function active
user-specific
Not in use
Preset adjustment function inactive
4.1.5 Origin Type
Specification of the measuring system origin (start of counting). A value different of "0"
causes a zero shift and it results a negative or positive offset.
CE_-65
CO_-65
lower limit
-1073741824 steps
-33554432000 steps
upper limit
1073741824 steps
33554432000 steps
default
0
0