[Parameter setting]
Title
Function
Adjustment range
Default setting
CW
Automatic acceleration/deceleration
0: Disabled (manual)
1: Automatic
2: Automatic (only at acceleration)
0
,
When automatically setting acceleration/deceleration time, always change the acceleration/deceleration
time so that it conforms with the load. The acceleration/deceleration time changes constantly with load
fluctuations. For inverters that requires a fixed acceleration/deceleration time, use the manual settings
(
CEE
,
FGE
).
,
Setting acceleration/deceleration time (
CEE
,
FGE
) in conformance with mean load allows optimum set-
ting that conforms to further changes in load.
,
Use this parameter after actually connecting the motor.
,
When the inverter is used with a load that fluctuates considerably, it may fail to adjust the acceleration or
deceleration time in time, and therefore may be tripped.
[Methods of setting automatic acceleration/deceleration]
Key operated
LED display
Operation
Displays the operation frequency.
(When standard monitor display selection
H
is set to
[Op-
eration frequency])
CWJ
The first basic parameter “
CWJ
” (history function) is displayed.
CWK
Press the key to change the parameter to
CWK
.
Pressing the ENTER key allows the reading of parameter setting.
Press the key to change the parameter to
or
.
⇔
CW
Press the ENTER key to save the changed parameter.
CW
and the
parameter are displayed alternately.
5.1.2 Manually setting acceleration/deceleration time
Set acceleration time from 0 (Hz) operation frequency to maximum frequency
HJ
and deceleration time as
the time when operation frequency goes from maximum frequency
HJ
to 0 (Hz).
Output frequency (Hz)
F
F
F
FGE
GE
GE
GE
C
C
C
CEE
EE
EE
EE
H
H
H
HJ
J
J
J
Time [sec]
O
CW
=
(Manual)
MODE