E6581158
F-71
6
6.19.13 Trip at VI/II low level input mode
H
: Trip at VI/II low level input mode
•
Function
The inverter will trip if the VIA value remains below the specified value for about 0.3 seconds. In such
a case, "
G
" is displayed.
H
=0: Disabled ........ The detection function is disabled.
H
=1-100 ................ The inverter will trip if the VIA value remains below the specified value for about
0.3 seconds.
Title
Function
Adjustment range
Default setting
H
Trip at VI/II low level input mode
0: Disabled
1-100%
0
Note : The VIA input value may be judged earlier to be abnormal, depending on the degree of deviation of
the analog data detected.
6.19.14 Calculation for life alarms
H
: Annual average ambient temperature (calculation for life alarms)
•
Function
You can set the inverter so that it will calculate the remaining useful lives of the cooling fan, main
circuit capacitor and on-board capacitor from the ON time of the inverter, the operating time of the
motor, the output current (load factor) and the setting of
H
, and that it will display and send out
an alarm through output terminals when each component is approaching the end of its useful life.
Title
Function
Adjustment range
Default setting
H
Annual average ambient temperature
(calculation for life alarms)
1: -10 to +10
°
C
2: 11-20
°
C
3: 21-30
°
C
4: 31-40
°
C
5: 41-50
°
C
6: 51-60
°
C
3
Note 1: Using
H
ѽ
enter the annual average temperature around the inverter. Be careful not to enter the
annual highest temperature
Note 2: Set
H
at the time of installation of the inverter, and do not change its setting after the start of
use. Changing the setting may cause a life alarm calculation error.