E6581158
L-1
12
12. Specifications
12.1
Models and their standard specifications
Q
Standard specifications
Item
Specification
Input voltage
3-phase 200V
Applicable motor (kW)
0.2
0.4
0.55
0.75
1.5
2.2
3.7
5.5
7.5
11
15
Type
VFS11
Form
2002PM
2004PM
2005PM
2007PM
2015PM
2022PM
2037PM
2055PM
2075PM
2110PM
2150PM
Capacity (kVA) Note 1)
0.6
1.3
1.4
1.8
3.0
4.2
6.7
10
13
21
25
Rated output/current
(A) Note 2)
1.5
(1.5)
3.3
(3.3)
3.7
(3.3)
4.8
(4.4)
8.0
(7.9)
11.0
(10.0)
17.5
(16.4)
27.5
(25.0)
33
(33)
54
(49)
66
(60)
Output voltage Note 3)
3-phase 200V to 240V
Rat
in
g
Overload current rating
150
%
-60 seconds, 200%-0.5 second (50%-reduction value)
Voltage-frequency
3-phase 200V to 240V - 50/60Hz
Po
w
e
r
s
upp
ly
Allowable fluctuation
V 10%, -15% Note 4), frequency ±5%
Protective method
IP20 Enclosed type (JEM1030)
Cooling method
Self-cooling
Forced air-cooled
Color
Munsel 5Y+8/0.5
Built-in filter
Basic filter
Item
Specification
Input voltage
1-phase 200V
3-phase 400V
Applicable motor (kW)
0.2
0.4
0.75
1.5
2.2
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11
15
Type
VFS11S
VFS11
Form
2002PL 2004PL 2007PL 2015PL 2022PL 4004PL 4007PL 4015PL 4022PL 4037PL 4055PL 4075PL 4110PL 4150PL
Capacity (kVA) Note 1)
0.6
1.3
1.8
3.0
4.2
1.1
1.8
3.1
4.2
7.2
11
13
21
25
Rated output current
(A) Note 2)
1.5
(1.5)
3.3
(3.3)
4.8
(4.4)
8.0
(7.9)
11.0
(10.0)
1.5
(1.5)
2.3
(2.1)
4.1
(3.7)
5.5
(5.0)
9.5
(8.6)
14.3
(13.0)
17.0
(17.0)
27.7
(25.0)
33
(
30
)
Rated output voltage Note 3)
3-phase 200V to 240V
3-phase 380V to 500V
Rat
in
g
Overload current rating
150
%
-60 seconds, 200%-0.5 second
(50%-reduction value)
150
%
-60 seconds, 200% -0.5 second (50%-reduction value)
Voltage-current
1-phase 200V to 240V – 50/60Hz
3-phase 380V to 500V - 50/60Hz
Po
w
e
r
s
upp
ly
Allowable fluctuation
V 10
%、
-15
%
Note 4),
frequency±5
%
V 10%, -15% Note 4), frequency ±5%
Protective method,
IP20 Enclosed type (JEM1030)
IP20 Enclosed type (JEM1030)
Cooling method
Self-cooling
Forced air-
cooled
Forced air-cooled
Color
Munsel 5Y+8/0.5
Munsel 5Y+8/0.5
Built-in filter
EMI filter
EMI filter
Note 1. Capacity is calculated at 220V for the 200V models and at 440V for the 400V models.
Note 2. Indicates rated output current setting when the PWM carrier frequency (parameter F300) is 4kHz or less. When ex-
ceeding 4kHz, the rated output current setting is indicated in the parentheses. It needs to be further reduced for PWM
carrier frequencies above 12 kHz.
The rated output current is reduced even further for 400V models with a supply voltage of 480V or more.
The default setting of the PWM carrier frequency is 12kHz.
Note 3. Maximum output voltage is the same as the input voltage.
Note 4. ±10% when the inverter is used continuously (load of 100%).