E6581158
F-67
6
6.19.9 Over-torque trip
H
: Over-torque trip/alarm selection
H
: Over-torque detection level
H
: Over-torque detection time
H
: Over-torque detection level hysteresis
•
Function
Use the
parameter to trip the inverter or to output the alarm if a torque currrent exceeding the
H
-specified level flows for more than the
H
-specified time. Trip information is displayed
as "
QV
".
H
=
: .......... No tripping (FL relay deactivated).
An over-torque alarm can be put out by setting the output terminal function selection
parameter.
H
=
: .......... The inverter is tripped (FL relay activated) only after a torque current exceeding the
H
-specified level has been detected for more than the
H
-specified time.
Title
Function
Adjustment range
Default setting
H
Over-torque trip/alarm selection
0: Alarm only
1: Tripping
0
H
Over-torque detection level
0-250 (%)
150
H
Over-torque detection time
0.0-10.0 [sec]
0.5
H
Over-torque detection level hysteresis
0-100 (%)
10