E6581158
F-3
6
6.1.2 Output of designated frequency reach signal
H
: Speed reach detection band
•
Function
When the output frequency becomes equal to the setting by designated frequency
±
H
, an ON or
OFF signal is generated.
Q
Parameter setting of designated frequency and detection band
Title
Function
Adjustment range
Default setting
H
Speed reach detection band
0.0
∼
HJ
(Hz)
2.5
Q
Parameter setting of output terminal selection
Title
Function
Adjustment range
Default setting
H
Output terminal
selection 2A
(OUT-NO)
0-255
(See Section 11, K-18)
6: RCH (designated frequency - ON signal), or
7: RCHN (designated frequency - OFF signal)
Note: Select the
H
parameter to specify RY-RC terminal output, or the
H
parameter to specify
FLA-FLC-FLB terminal output.
Output frequency [Hz]
Time [s]
Designated frequency
−
H
ON
OFF
Designated frequency
+
H
Designated frequency
Set frequency speed reach signal
P24-OUT (Default setting)
RY-RC
FLA/FLC/DLB
Set frquency spped reach signal:
Inverted
ON
OFF
0