E6581158
F-5
6
6.2
Input signal selection
6.2.1 Priority selection (both F-CC, R-CC are ON)
H
: Priority selection (both F-CC, R-CC are ON)
•
Function
This parameter allows you to select the direction in which the motor runs when a forward run (F)
command and a reverse run (R) command are entered simultaneously.
1) Reverse
2) Slowdown stop
Q
Parameter setting
Title
Function
Adjustment range
Default setting
H
Priority selection (both F-CC, R-CC
are ON)
0: Reverse
1: Slowdown stop
1
[
H
=
(Stop)]: If an F command and an R command are entered simultaneously,
the motor will slow down to a stop.
Forward run
Reverse run
Run forward signal
Run backward signal
ON
OFF
ON
OFF
Output frequency [Hz]
Set frequency
Time[s]
0