How to install
Install the inverter in a well-ventilated indoor place and mount it on a flat metal plate in portrait orientation.
If you are installing more than one inverter, the separation between inverters should be at least 5 centimeters, and
they should be arranged in horizontal rows. If the inverters are horizontally arranged with no space between
them (side-by-side installation), peel of the ventilation seals on top of the inverter. It is necessary to de-
crease the current if the inverter is operated at over 40°C. For more information, refer to “Load Reduction
and Thermal Environment Instruction Manual.”
••••
Standard installation
••••
Horizontal installation (side-by-side installation)
5 centimeters or more
5 centimeters or more
10 centimeters or more
10 centimeters or more
Remove seals on top
VFS11
VFS11
VFS11
VFS11
10 centimeters or more
10 centimeters or more
The space shown in the diagram is the minimum allowable space. Because air cooled equipment has cooling
fans built in on the top or bottom surfaces, make the space on top and bottom as large as possible to allow
for air passage.
Note:
Do not install in any location where there is high humidity or high temperatures and where there are
large amounts of dust, metallic fragments and oil mist. If you are going to install the equipment in any
area that presents a potential problem, please consult with Toshiba before doing so.