Auto-stop in case of lower-limit frequency continuous
operation
6.8.1 Auto-stop in case of lower-limit frequency continuous
operation
H
: Auto-stop in case of lower-limit frequency continuous operation
•
Function
If operation is carried out continuously at a frequency below the lower-limit frequency (
NN
) for the period
of time set with
H
, the inverter will automatically slow down the motor to a stop. At that time,
“
NUVR
” is displayed (alternately) on the operation panel.
This function will be canceled if a frequency command above the lower-limit frequency (
NN
).
[Parameter setting]
Title
Function
Adjustment range
Default setting
H
Auto-stop in case of lower-limit fre-
quency continuous operation time
0.0: None
0.1-600.0 (sec.)
0.0
Note: This function is enabled even at the start of operation and during switching between forward and re-
verse run.