Troubleshooting
Confirmation and check
When an error occurred in the Air to Air Heat
Exchanger with DX Coil Unit, the check code and the
indoor unit No. appear on the display part of the remote
controller.
The check code is only displayed during the operation.
If the display disappears, operate the Air to Air Heat
Exchanger with DX Coil Unit according to the following
“Confirmation of error log” for confirmation.
Confirmation of error log
When an error occurred on the Air to Air Heat
Exchanger with DX Coil Unit, the error log can be
confirmed with the following procedure. (The error log
is stored in memory up to 4 errors.)
The log can be confirmed from both operating status
and stop status.
1
When
and
buttons are pushed
simultaneously for 4 seconds or more, the
following display appears.
If [Service check]
is displayed, the mode
enters in the error log mode.
• [
01
: Order of error log] is displayed in CODE No.
window.
• [Check code] is displayed in CHECK window.
• [Air to Air Heat Exchanger with DX Coil Unit
address in which an error occurred] is displayed
in Unit No.
2
Every pushing of
button used to set
temperature, the error log stored in memory
is displayed in order.
The numbers in CODE No. indicate CODE No.
[
01
] (latest)
→
[
04
] (oldest).
REQUIREMENT
Do not push
button because all the error log of the
Air to Air Heat Exchanger with DX Coil Unit will be
deleted.
3
After confirmation, push
button to return
to the usual display.
Check code
Unit No. of the Air to Air Heat Exchanger
with DX Coil Unit with a problem
3
2
1
How to check
To display an error code or to confirm the operation status, the remote controller (wired remote controller and
central remote controller) is equipped with an LCD display, and the interface circuit board of the outdoor unit is
equipped with a 7 segment display. A self-diagnosis function is activated to find out the details of a problem with
the unit.
Error code list
The table below shows the error codes. See the table for details of error codes.
• To confirm the code from the remote controller, see “Wired remote controller display” in the table.
• To confirm the code from the outdoor unit, see “7 segment display on the outdoor unit” in the table.
Wired
remote
controller
display
Check code
Check code name
Judging
device
7 segment display on the
outdoor unit
Auxiliary code
E01
—
—
Indoor unit - remote controller communication error (Detected by
remote controller)
Remote
controller
E02
—
—
Remote control transmission error
Remote
controller
E03
—
—
Indoor unit - remote controller communication error (Detected by indoor
unit)
Indoor
E04
—
—
Indoor / Outdoor unit communication circuit error (Detected by indoor
unit)
Indoor
E06
E06
Number of indoor units for
normal reception
Number of indoor units decreasing
I/F
—
E07
—
Indoor / Outdoor unit communication circuit error (Detected by outdoor
unit)
I/F
E08
E08
Duplicate indoor addresses Duplicate indoor addresses
Indoor I/F
E09
—
—
Duplicate header remote controllers
Remote
controller
E10
—
—
Indoor MCU communication error
Indoor
E12
E12
01: Indoor / Outdoor unit
communication
02: Communications
between outdoor units
Automatic address start error
I/F
E15
E15
—
No indoor unit during automatic address
I/F
E16
E16
00: Over capacity
01
~: Number of connected
units
Number of connected units / Over capacity
I/F
E18
—
—
Indoor header - follower communication error
Indoor
E19
E19
00: No center unit
02: Multiple center units
Unusual number of center outdoor units
I/F
E20
E20
01: Outdoor connections of
another line
02: Indoor connections of
another line
Connections of another line during automatic address
I/F
E21
E21
02: No header unit
00: Number of duplicate
header units
Unusual number of thermal header units
I/F
E22
E22
—
Number of thermal units decreasing
I/F
E23
E23
—
Transmission error between outdoor units Number of thermal units error
(Reception error)
I/F
E25
E25
—
Duplicate terminal outdoor address settings
I/F
E26
E26
Number of outdoor units for
normal reception
Number of connected outdoor units decreasing
I/F
E28
E28
Detected outdoor unit No.
Terminal outdoor error
I/F