– 7 –
Air to Air Heat Exchanger with DX Coil Unit
Installation Manual
Air to Air Heat Exchanger with DX Coil Unit
Installation Manual
Unit: mm
Center of gravity
Model No.
A
B
C
D
E
F
MMD-VNK502HEXE-TR, VN502HEXE-TR
1,690
1140
1140
250
175
350
MMD-VNK802HEXE-TR, VN802HEXE-TR
1,739
1189
1189
275
200
400
MMD-VNK1002HEXE-TR, VN1002HEXE-TR
1,739
1189
1189
275
200
400
Model No.
G
H
I
J
K
Duct
diameter
Diameter of
refrigerant
piping at the
gas side (L)
Diameter of
refrigerant
piping at the
liquid side (M)
MMD-VNK502HEXE-TR, VN502HEXE-TR
175
Ø195
Ø212
1601
1197
Ø200
Ø9.5
Ø6.4
MMD-VNK802HEXE-TR, VN802HEXE-TR
200
Ø245
Ø262
1650
1246
Ø250
Ø12.7
Ø6.4
MMD-VNK1002HEXE-TR, VN1002HEXE-TR
200
Ø245
Ø262
1650
1246
Ø250
Ø12.7
Ø6.4
Model No.
X
Y
Z
Weight
MMD-VNK502HEXE-TR
902
643
174
91
MMD-VNK802HEXE-TR
901
667
199
111
MMD-VNK1002HEXE-TR
900
667
199
112
MMD-VN502HEXE-TR
870
642
174
84
MMD-VN802HEXE-TR
856
663
198
100
MMD-VN1002HEXE-TR
853
663
198
101
X
Y
Z
Installing the indoor unit
Attaching the duct connector
Attach 4 duct connectors to the unit using the six screws supplied for each connector.
Attaching the washers and nuts
1
Procure the hanging bolts, nuts, and washers locally.
2
Attach the washers and nuts to the hanging bolt (M12) as shown in the figure on the right.
Fixing the unit
1
Fit the hanging bracket on the hanging bolt, then adjust the position of the unit so that it is level.
2
Tighten the bolts securely using a double nut to prevent the bolts from becoming loose.
• If the bolts are not tightened securely, the unit will vibrate and an accident may occur.
• Tighten the bolts so that they can bear the weight of the unit.
3
Confirm that the unit is installed level.
• Confirm that the unit is installed level or is inclined within 1°(downward) against the drain outlet using a spirit
level.
• Do not set the unit inclined (upward) against the drain outlet; otherwise, water will leak from the unit.
CAUTION
To preventing vibration, use vibration proof hanging brackets (locally procured).
Duct connector
Screws
Hanging bolt
(M12)
Nut
Washer
Nut
Within 1°
Within 1°
Hanging bolt (Ø12)
Nut
Washer
Washer
Nut
Hanging bracket
Vibration-
proof hanging
bracket
Hanging bolt (Ø12)
Vibration-proof hanging
bracket
13-EN
14-EN