Louver control:
Outline of specifications
1) Louver position setup
• When the louver position is changed, the position moves
necessarily to downward discharge position once to return to
the set position.
• The louver position can be set up in the following operation
range.
Remarks
The louver position at
horizontal discharge
position at under
UP
30
differs from that at over
UP
036.
In cooling/dry operation
In heating/fan operation
• In group twin/triple operation, the louver positions can be set
up collectively or individually.
In case that HEAT refrigerant recovery control was per-
formed in STOP status, the louver position becomes
horizontal when the operation is resumed.
2) Swing setup
• [SWING] is displayed and the following display is repeated.
In all operations
(Repeats)
• In group operation, the louver positions can be set up
collectively or individually.
3) When the unit stopped or the warning was output, the louver is
automatically set to full closed position.
4) When PRE-HEAT (Heating ready) is displayed
(Heating operation started or defrost operation is performed),
heating thermo is off or self-cleaning is performed, the louver is
automatically set to horizontal discharge position.
* The louver which air direction is individually set or the locked
louver closes fully when the unit stops and the louver is
automatically set to horizontal discharge position when PRE-
HEAT (Heating ready) is displayed, heating thermo is off.
<<Individual air direction setup>>
[02]
E
E-
-b
box
ox
[04]
Refrigerant pipe
Drain pipe
[01]
[03]
• Pushing
UNIT
LOUVER
Louver select button enables every discharge
port to set up the air direction.
The louver numbers that are displayed on the display part
correspond to those in the following figure.
• In case of no input (key operation) for approx. 5 seconds during
setting of individual air direction (during displaying of louver No.
on the remote controller screen), the remote controller screen
returns to the normal display screen.
• For the air direction illustration during normal operation, the air
direction of the least No. among the louvers
which are block-set is displayed.
• While individual air direction is being set,
the remote controller operation
(Illustration of air direction) and operation
of the real machine are linked.
• When selecting a case,
UNIT
LOUVER
Louver
select button is not pushed or louver No.
is not displayed, the air directions of all
the louvers are ollectively set up.
The swinging louver
moves usually up to the
ceiling side from the
louver position of the set
time.
Setup from the remote
controller without
UNIT
LOUVER
button is unavailable.
For the setup operation,
refer to “How to set up
louver individually” of Item
“Setup at local site/
Others”.
- 75 -
Содержание MMC-UP0151HP-E
Страница 41: ...2 2 Ceiling type MMC UP0151HP E TR MMC UP0181HP E TR 41 ...
Страница 42: ...MMC UP0241HP E TR MMC UP0271HP E TR 6 4 12 7 42 ...
Страница 43: ...MMC UP0361HP E TR MMC UP0481HP E TR MMC UP0561HP E TR 43 ...
Страница 58: ...3 WIRING DIAGRAMS 3 1 4 way cassette type MMU UP HP E TR 58 ...
Страница 59: ...3 2 Ceiling type MMC UP HP E TR 59 ...
Страница 60: ...3 3 Concealed Duct Standard type MMD UP BHP E TR 60 ...
Страница 61: ...3 4 Concealed Duct High Static Pressure type MMD UP HP E TR 61 ...
Страница 62: ...Concealed Duct High Static Pressure type MMD UP HP E TR 62 ...
Страница 63: ...3 5 Concealed Duct High Static Pressure fresh air intake type MMD UP HFP E TR 63 ...
Страница 65: ...3 7 High wall type MMK UP HP E TR 65 ...
Страница 247: ...MMU UP0241HP E TR MMU UP0271HP E TR MMU UP0301HP E TR 211 233 252 253 251 254 255 213 216 263 247 ...
Страница 249: ...MMU UP0361HP E TR MMU UP0481HP E TR MMU UP0561HP E TR 268 267 213 214 249 ...
Страница 252: ...12 2 Ceiling type MMC UP0151HP E TR MMC UP0181HP E TR 025 024 252 ...
Страница 254: ...MMC UP0241HP E TR MMC UP0271HP E TR 029 028 254 ...
Страница 256: ...MMC UP0361HP E TR MMC UP0481HP E TR MMC UP0561HP E TR 051 028 027 256 ...
Страница 261: ...MMD UP0151BHP E TR MMD UP0181BHP E TR 240 239 238 233 235 261 ...
Страница 263: ...MMD UP0241BHP E TR MMD UP0271BHP E TR MMD UP0301BHP E TR 240 239 238 233 235 263 ...
Страница 265: ...MMD UP0361BHP E TR MMD UP0481BHP E TR MMD UP0561BHP E TR 240 239 238 233 235 265 ...
Страница 289: ...MMK UP0031HPL E TR MMK UP0051HPL E TR MMK UP0071HPL E TR MMK UP0091HPL E TR MMK UP0121HPL E TR 289 ...
Страница 295: ...144 9 MOO 5 BANGKADI INDUSTRIAL PARK TIVANON ROAD TAMBOL BANGKADI AMPHUR MUANG PATHUMTHANI 12000 THAILAND ...