No.
17
Item
Display of
[READY]
[HEAT READY]
Outline of specifications
< READY>
Displayed on the remote controller
1) When the following check codes are indicated
• Open phase of power supply wiring [P05] was detected.
• There is an indoor unit that detected the indoor overflow
[P10].
• There is an indoor unit that detected the interlock alarm
[L30].
2) During Force Thermostat-OFF
• [COOL/DRY] operation is unavailable because the other
indoor unit operates with [HEAT] mode.
• [HEAT] operation is unavailable because COOL priority
(SW11-bit1 of the Outdoor I/F P. C. board is ON) is set and
the other indoor unit operates with [COOL/DRY] mode.
3) The above indoor units that cannot operate stay in
Thermostat-OFF status.
4) The indoor fan stops because the system performs
[Recovery operation for heating refrigerant (Oil)].
<HEAT READY>
Displayed on the remote controller
The indoor fan stops in order to prevent discharge of cool air
when heating operation started or during heating operation.
(including the defrost operation during thermostat-OFF)
1) Selection of the contents that can be operated by the
remote controller at the indoor unit side is possible
according to setting at the central controller side.
2) Setting contents
Remarks
•
< READY >
display
No display for wireless
type remote controller
•
<HEAT READY >
display
(
: Operation possible
: Operation impossible)
Selection of
central control
mode
18
Operation from
central controller
Individual
[Central 1]
[Central 2]
[Central 3]
[Central 4]
Operation on remote controller
ON/OFF
Operation
Timer
Temp.
Fan speed
Air direction
setting
selection
setting
setting
setting
setting
Display of filter
sign [
]
(Not provided to
the wireless
type)
1) The filter sign is displayed with LC by sending the filter-
reset signal to the remote controller when the specified
time (150H/2500H) elapsed as a result of integration of the
operation time of the indoor fan.
2) The integrated timer is cleared when the filter-reset signal is
received from the remote controller.
In this time, if the specified time elapsed, the counted time is
reset and the liquid crystal display is deleted.
[
The filter sign is not
displayed in
RBC-ASCU11-
∗
.
FILTER] goes on.
16
Alarm output
setup
DN
Alarm output of the
header indoor unit
Setting data
The alarm output from the indoor P.C. board is output in each
indoor unit during group control, but it can be set so as to be
output in the header unit and follower units.
Following the table below, register the setting data in DN Code "79".
Connector CN61
(Refer to
8-3-1,8-3-2. Optional
connector specifications of
indoor P.C.board
(MCC-1643, MCC-1744
)
Be
sure to change the setting
data while operation
stops.
15
79
Not including the state of follower units
0000 (Factory default)
Including the state of follower units
0001
- 74 -
Содержание MMC-UP0151HP-E
Страница 41: ...2 2 Ceiling type MMC UP0151HP E TR MMC UP0181HP E TR 41 ...
Страница 42: ...MMC UP0241HP E TR MMC UP0271HP E TR 6 4 12 7 42 ...
Страница 43: ...MMC UP0361HP E TR MMC UP0481HP E TR MMC UP0561HP E TR 43 ...
Страница 58: ...3 WIRING DIAGRAMS 3 1 4 way cassette type MMU UP HP E TR 58 ...
Страница 59: ...3 2 Ceiling type MMC UP HP E TR 59 ...
Страница 60: ...3 3 Concealed Duct Standard type MMD UP BHP E TR 60 ...
Страница 61: ...3 4 Concealed Duct High Static Pressure type MMD UP HP E TR 61 ...
Страница 62: ...Concealed Duct High Static Pressure type MMD UP HP E TR 62 ...
Страница 63: ...3 5 Concealed Duct High Static Pressure fresh air intake type MMD UP HFP E TR 63 ...
Страница 65: ...3 7 High wall type MMK UP HP E TR 65 ...
Страница 247: ...MMU UP0241HP E TR MMU UP0271HP E TR MMU UP0301HP E TR 211 233 252 253 251 254 255 213 216 263 247 ...
Страница 249: ...MMU UP0361HP E TR MMU UP0481HP E TR MMU UP0561HP E TR 268 267 213 214 249 ...
Страница 252: ...12 2 Ceiling type MMC UP0151HP E TR MMC UP0181HP E TR 025 024 252 ...
Страница 254: ...MMC UP0241HP E TR MMC UP0271HP E TR 029 028 254 ...
Страница 256: ...MMC UP0361HP E TR MMC UP0481HP E TR MMC UP0561HP E TR 051 028 027 256 ...
Страница 261: ...MMD UP0151BHP E TR MMD UP0181BHP E TR 240 239 238 233 235 261 ...
Страница 263: ...MMD UP0241BHP E TR MMD UP0271BHP E TR MMD UP0301BHP E TR 240 239 238 233 235 263 ...
Страница 265: ...MMD UP0361BHP E TR MMD UP0481BHP E TR MMD UP0561BHP E TR 240 239 238 233 235 265 ...
Страница 289: ...MMK UP0031HPL E TR MMK UP0051HPL E TR MMK UP0071HPL E TR MMK UP0091HPL E TR MMK UP0121HPL E TR 289 ...
Страница 295: ...144 9 MOO 5 BANGKADI INDUSTRIAL PARK TIVANON ROAD TAMBOL BANGKADI AMPHUR MUANG PATHUMTHANI 12000 THAILAND ...