Check code
Location
of
detection
Description
System status
Check code detection
condition(s)
Check items (locations)
• Check outdoor unit model.
(Check whether the
outdoor unit corresponds
to Air to Air Heat
Exchanger type or not.)
Outdoor units
model
disagreement
trouble
Indoor unit
Stop of
corresponding
unit
In case of different outdoor
unit (Not corresponded to
Air to Air Heat Exchanger
type)
L02
L02
—
• Check indoor addresses.
• Check for any change
made to remote controller
connection (group/
individual) since indoor
address setting.
Duplicated
indoor header
unit
Indoor unit
Stop of
corresponding
unit
There are more than one
header units in group.
L03
—
—
• Check power supply
voltage.
(AC380V-415V ± 10%).
• Check for failure in
compressor.
• Check for possible cause
of abnormal overloading.
• Check for failure in outdoor
P.C. board (compressor).
Compressor
trouble
(Step-out)
Compressor
P.C. board
1
∗
: Compressor
1
side
2
∗
: Compressor
2
side
All stop
Judged that the
synchronization could not be
taken.
H17
H17
• Check line addresses.
Duplicated
outdoor line
address
I/F
All stop
There is duplication in line
address setting for outdoor
units belonging to different
refrigerant piping systems.
L04
L04
—
• Check display on priority
indoor unit.
Duplicated
priority indoor
unit (as
displayed on
priority indoor
unit)
I/F
All stop
More than one indoor units
have been set up as priority
indoor unit.
L05
—
—
• Check displays on priority
indoor unit and outdoor
unit.
Duplicated
priority indoor
unit (as
displayed on
indoor unit other
than priority
indoor unit)
I/F
No. of priority
indoor units
All stop
More than one indoor units
have been set up as priority
indoor unit.
L06
L06
• Check indoor addresses.
Connection of
group control
cable to
standalone
indoor unit
Indoor unit
Stop of
corresponding
unit
There is at least one
standalone indoor unit to
which group control cable is
connected.
L07
—
—
• Check indoor addresses.
Note:
This code is displayed
when power is turned on
for the first time after
installation.
Indoor group /
addresses not
set
Indoor unit
Stop of
corresponding
unit
Address setting has not
been performed for indoor
units.
L08
L08
—
Set indoor capacity. (DN =
11)
Indoor capacity
not set
Indoor unit
Stop of
corresponding
unit
Capacity setting has not
been performed for indoor
unit.
L09
—
—
Main
remote
controller
Outdoor 7-segment display
Check
code
Sub-code
• Check for disconnection of
TK1 sensor.
• Check resistance
characteristics of TK1
sensor.
• Check for connection
trouble involving TK1 and
TK2 sensors
• Check for clogging in oil
equalizing circuit capillary.
• Check for refrigerant
entrapment inside
compressor.
Oil level
detection
circuit trouble
I/F
01: TK1 oil
circuit trouble
02: TK2 oil
circuit trouble
All stop
No temperature change is
detected by TK1 despite
compressor 1 having been
started.
H16
H16
• Check for disconnection of
TK2 sensor.
• Check resistance
characteristics of TK2
sensor.
• Check for connection
trouble involving TK1 and
TK2 sensors
• Check SV3F valve
malfunction.
• Check for clogging in oil
equalizing circuit capillary.
• Check for refrigerant
entrapment inside
compressor.
No temperature change is
detected by TK2 despite
compressor 2 having been
started.
- 143 -
Содержание MMC-UP0151HP-E
Страница 41: ...2 2 Ceiling type MMC UP0151HP E TR MMC UP0181HP E TR 41 ...
Страница 42: ...MMC UP0241HP E TR MMC UP0271HP E TR 6 4 12 7 42 ...
Страница 43: ...MMC UP0361HP E TR MMC UP0481HP E TR MMC UP0561HP E TR 43 ...
Страница 58: ...3 WIRING DIAGRAMS 3 1 4 way cassette type MMU UP HP E TR 58 ...
Страница 59: ...3 2 Ceiling type MMC UP HP E TR 59 ...
Страница 60: ...3 3 Concealed Duct Standard type MMD UP BHP E TR 60 ...
Страница 61: ...3 4 Concealed Duct High Static Pressure type MMD UP HP E TR 61 ...
Страница 62: ...Concealed Duct High Static Pressure type MMD UP HP E TR 62 ...
Страница 63: ...3 5 Concealed Duct High Static Pressure fresh air intake type MMD UP HFP E TR 63 ...
Страница 65: ...3 7 High wall type MMK UP HP E TR 65 ...
Страница 247: ...MMU UP0241HP E TR MMU UP0271HP E TR MMU UP0301HP E TR 211 233 252 253 251 254 255 213 216 263 247 ...
Страница 249: ...MMU UP0361HP E TR MMU UP0481HP E TR MMU UP0561HP E TR 268 267 213 214 249 ...
Страница 252: ...12 2 Ceiling type MMC UP0151HP E TR MMC UP0181HP E TR 025 024 252 ...
Страница 254: ...MMC UP0241HP E TR MMC UP0271HP E TR 029 028 254 ...
Страница 256: ...MMC UP0361HP E TR MMC UP0481HP E TR MMC UP0561HP E TR 051 028 027 256 ...
Страница 261: ...MMD UP0151BHP E TR MMD UP0181BHP E TR 240 239 238 233 235 261 ...
Страница 263: ...MMD UP0241BHP E TR MMD UP0271BHP E TR MMD UP0301BHP E TR 240 239 238 233 235 263 ...
Страница 265: ...MMD UP0361BHP E TR MMD UP0481BHP E TR MMD UP0561BHP E TR 240 239 238 233 235 265 ...
Страница 289: ...MMK UP0031HPL E TR MMK UP0051HPL E TR MMK UP0071HPL E TR MMK UP0091HPL E TR MMK UP0121HPL E TR 289 ...
Страница 295: ...144 9 MOO 5 BANGKADI INDUSTRIAL PARK TIVANON ROAD TAMBOL BANGKADI AMPHUR MUANG PATHUMTHANI 12000 THAILAND ...