No.
Part name
P
rocedure
s
Remarks
Vertical louver
assembly
Cross flow fan
3.5 mm
Cross flow fan
Set screw
Fan motor
Body back
1) Follow the procedure item 3 and 4 .
2) Loosen the set screw of the cross flow fan.
3) Remove 4 fixing screws from the bearing
base then remove it from the main unit.
<To re-installation>
1) To incorporate the fan motor and the
motor into the position in the following
figure.
- Install the cross flow fan so that the right
end of the 1st joint from the right of the
Cross flow fan is keep 3.5mm from
closed wall of the main unit.
- Holding the set screw, install the
cross flow fan so that flat area on shaft of
the fan motor comes to the mounting hole
of the set screw.
4) Lift up the heat exchanger follow the figure.
Pull out the left hand side until the cross flow
fan is released from the shaft of the fan
motor and then pull out the lower side of
heat exchanger follow the figure.
8
9
1) Follow the procedure item 3 and 7 .
2) Remove 2 fixing screws from the base vertical
louver then remove the vertical louver
assembly from the body back.
Vertical louver
Screw
Screw
Heat exchanger
Cross flow fan
Bearing base
Heat exchanger
Cross flow fan
- 236 -
Содержание MMC-UP0151HP-E
Страница 41: ...2 2 Ceiling type MMC UP0151HP E TR MMC UP0181HP E TR 41 ...
Страница 42: ...MMC UP0241HP E TR MMC UP0271HP E TR 6 4 12 7 42 ...
Страница 43: ...MMC UP0361HP E TR MMC UP0481HP E TR MMC UP0561HP E TR 43 ...
Страница 58: ...3 WIRING DIAGRAMS 3 1 4 way cassette type MMU UP HP E TR 58 ...
Страница 59: ...3 2 Ceiling type MMC UP HP E TR 59 ...
Страница 60: ...3 3 Concealed Duct Standard type MMD UP BHP E TR 60 ...
Страница 61: ...3 4 Concealed Duct High Static Pressure type MMD UP HP E TR 61 ...
Страница 62: ...Concealed Duct High Static Pressure type MMD UP HP E TR 62 ...
Страница 63: ...3 5 Concealed Duct High Static Pressure fresh air intake type MMD UP HFP E TR 63 ...
Страница 65: ...3 7 High wall type MMK UP HP E TR 65 ...
Страница 247: ...MMU UP0241HP E TR MMU UP0271HP E TR MMU UP0301HP E TR 211 233 252 253 251 254 255 213 216 263 247 ...
Страница 249: ...MMU UP0361HP E TR MMU UP0481HP E TR MMU UP0561HP E TR 268 267 213 214 249 ...
Страница 252: ...12 2 Ceiling type MMC UP0151HP E TR MMC UP0181HP E TR 025 024 252 ...
Страница 254: ...MMC UP0241HP E TR MMC UP0271HP E TR 029 028 254 ...
Страница 256: ...MMC UP0361HP E TR MMC UP0481HP E TR MMC UP0561HP E TR 051 028 027 256 ...
Страница 261: ...MMD UP0151BHP E TR MMD UP0181BHP E TR 240 239 238 233 235 261 ...
Страница 263: ...MMD UP0241BHP E TR MMD UP0271BHP E TR MMD UP0301BHP E TR 240 239 238 233 235 263 ...
Страница 265: ...MMD UP0361BHP E TR MMD UP0481BHP E TR MMD UP0561BHP E TR 240 239 238 233 235 265 ...
Страница 289: ...MMK UP0031HPL E TR MMK UP0051HPL E TR MMK UP0071HPL E TR MMK UP0091HPL E TR MMK UP0121HPL E TR 289 ...
Страница 295: ...144 9 MOO 5 BANGKADI INDUSTRIAL PARK TIVANON ROAD TAMBOL BANGKADI AMPHUR MUANG PATHUMTHANI 12000 THAILAND ...