No.
Part to be replaced
Work procedure
Remarks
⑦
Fan motor, fan
1. Detachment
1) Remove the electric parts box cover.
(see the 1. of
①
)
2) Disconnect the leads for the fan motor from the fan
control board.
CN703 : Fan motor (leads : Black), W
CN704 : Fan motor (leads: White), V
CN705 : Fan motor (leads: Red), U
Note
Unlock the locks on the housing to remove
the connector.
3) Remove the ferrite core from the leads of the fan
motor.
Note
After replacing the fan motor, re-connect
motor leads with the ferrite core rang
around the leads by 1 loop.
4) Remove the bottom plate (suction side).
(see the 1. of No.
⑥
)
5) Remove the screws A (8 pcs), and loosen the screws
B (2 pcs). Don’t remove the screws B (2 pcs) since
they are used as hooks later.
6) Remove the fan assembly.
Fan assembly
Caution
The fan assembly weighs 30 kg.
Be sure that the work is performed by two
persons or more with great care.
7) Remove the screws C (8 pcs).
8)
9)
Loosen the hexagonal bolts (2 pcs) which secure the
fan to the motor shaft, and remove the fan from the
motor shaft.
Remove the screws D (4 pcs) for the fan case, and
remove the fan after removing the nose plate.
10) Remove the earthing screw for the fan motor.
11) Remove the screws E (2 pcs), and remove the motor
anchor plate and the fan motor.
Fan motor leads
CN703
CN704
CN705
Ferrite core
Screw B
Screw A
Screw C (also on the other side)
Fan case
Hexagonal bolt
Screw D
Nose plate
Motor anchor plate
Earthing screw
Fan motor
Screw E
- 217 -
Содержание MMC-UP0151HP-E
Страница 41: ...2 2 Ceiling type MMC UP0151HP E TR MMC UP0181HP E TR 41 ...
Страница 42: ...MMC UP0241HP E TR MMC UP0271HP E TR 6 4 12 7 42 ...
Страница 43: ...MMC UP0361HP E TR MMC UP0481HP E TR MMC UP0561HP E TR 43 ...
Страница 58: ...3 WIRING DIAGRAMS 3 1 4 way cassette type MMU UP HP E TR 58 ...
Страница 59: ...3 2 Ceiling type MMC UP HP E TR 59 ...
Страница 60: ...3 3 Concealed Duct Standard type MMD UP BHP E TR 60 ...
Страница 61: ...3 4 Concealed Duct High Static Pressure type MMD UP HP E TR 61 ...
Страница 62: ...Concealed Duct High Static Pressure type MMD UP HP E TR 62 ...
Страница 63: ...3 5 Concealed Duct High Static Pressure fresh air intake type MMD UP HFP E TR 63 ...
Страница 65: ...3 7 High wall type MMK UP HP E TR 65 ...
Страница 247: ...MMU UP0241HP E TR MMU UP0271HP E TR MMU UP0301HP E TR 211 233 252 253 251 254 255 213 216 263 247 ...
Страница 249: ...MMU UP0361HP E TR MMU UP0481HP E TR MMU UP0561HP E TR 268 267 213 214 249 ...
Страница 252: ...12 2 Ceiling type MMC UP0151HP E TR MMC UP0181HP E TR 025 024 252 ...
Страница 254: ...MMC UP0241HP E TR MMC UP0271HP E TR 029 028 254 ...
Страница 256: ...MMC UP0361HP E TR MMC UP0481HP E TR MMC UP0561HP E TR 051 028 027 256 ...
Страница 261: ...MMD UP0151BHP E TR MMD UP0181BHP E TR 240 239 238 233 235 261 ...
Страница 263: ...MMD UP0241BHP E TR MMD UP0271BHP E TR MMD UP0301BHP E TR 240 239 238 233 235 263 ...
Страница 265: ...MMD UP0361BHP E TR MMD UP0481BHP E TR MMD UP0561BHP E TR 240 239 238 233 235 265 ...
Страница 289: ...MMK UP0031HPL E TR MMK UP0051HPL E TR MMK UP0071HPL E TR MMK UP0091HPL E TR MMK UP0121HPL E TR 289 ...
Страница 295: ...144 9 MOO 5 BANGKADI INDUSTRIAL PARK TIVANON ROAD TAMBOL BANGKADI AMPHUR MUANG PATHUMTHANI 12000 THAILAND ...