66
G2020 Series UPS Installation and Operation Manual
– 94861-004
Code
indication
(Note 3)
LCD Screen Status
Message
Meaning
Recommended
Action
Buzzer
External relay
contact
(Note 1)
Failure
lamp
(Note 2)
UF401
52S ABNORMAL
Error to close the contactor 52S.
CALL SERVICE
ENGINEER
Continuous
sound
Major
Cont. On
UF402
52S ABNORMAL
Error to open the contactor 52S.
CALL SERVICE
ENGINEER
Continuous
sound
Major
Cont. On
UF420
52L OPERATION
ERROR
Load circuit breaker 52L opened
during inverter operation.
CHECK 52L
Continuous
sound
Major
Cont. On
UF451
52S ABNORMAL
Contactor 52S failed during load
transfer from inverter to bypass.
CALL SERVICE
ENGINEER
Intermittent
sound
Minor
Blinking
UF452
CB3 ABNORMAL
Contactor CB3 is not working
properly.
CALL SERVICE
ENGINEER
Intermittent
sound
Minor
Blinking
(Note 1) 1) "Major" is defined as a major failure. Load transferred from the inverter circuit to the static bypass line;
2) "Minor" is defined as a minor failure. UPS continues to operate normally, but cause of alarm is identified;
(Note 2) Indicates one of two possible LED illumination patterns
– continuously on (Cont. On) or intermittent (Blinking).
(Note 3) Code indication means:
UA+++ ------------------------ Alarm
UF+++ ------------------------ Failure
U%0++ ----------------------- Rectifier circuit failure
U%1++ ----------------------- DC circuit failure
U%2++ ----------------------- Inverter circuit failure
U%3++ ----------------------- Control circuit failure
U%4++ ----------------------- Bypass system failure
U%8++ ----------------------- Alarm
U%+00 - U%+49 --------- Major failure
U%+50 - U%+99 --------- Minor failure
*)
“+” denotes any numeral from 0 to 9
*)
“%” denotes either “A” or “F”
Содержание G2020 Series
Страница 2: ......
Страница 78: ...70 G2020 Series UPS Installation and Operation Manual 94861 004 ...
Страница 83: ......
Страница 84: ......
Страница 85: ......