G2020 Series UPS Installation and Operation Manual
– 94861-004
55
a.
b.
Figure 5-13 Automatic Startup of Inverter and Converter
f) Close the Battery Breaker. (The START/STOP icon will not work until the battery breaker is closed.)
The display will show CB2 is closed and the battery backup is now online. (Figure 5-14)
Figure 5-14 Close Battery Breaker
g) Press the STOP/START icon on the display, then press and hold the START button (Figure 5-15a) for two (2) seconds
until the UPS transfers to load on INV. (Figure 5-15b)
a.
b.
Figure 5-15 Press and Hold START Button