G2020 Series UPS Installation and Operation Manual
– 94861-004
17
3.3
SPECIFICATIONS
The UPS nameplate displays the rated kVA as well as nominal voltages and currents. The nameplate is located on the
backside of the UPS front left door.
Table 3-1 Power Specifications
Rated output
Power
Input voltage
3 phase / 3 wire
Bypass input voltage
3 phase / 3 wire
Output voltage
3 phase / 3 wire
500kVA / 500kW
480V
480V
480V
750kVA / 750kW
480V
480V
480V
Table 3-2 UPS Module Information
UPS
[kVA]
Width
[in. (mm)]
Depth
[in. (mm)]
Height
[in. (mm)]
Net Weight
[lbs. (kg)]
Typ. Heating
at 100% load
[kBTU/h]
Cable
Knockout
500
59.1
(1,500)
33.5
(850)
80.6
(2,047)
2,756
(1,250)
31.2
BOTTOM
TOP
LEFT SIDE
750
81.6
(2,073)
33.5
(850)
80.6
(2,047)
3,990
(1,810)
46.8
BOTTOM
TOP
LEFT SIDE
Table 3-3 UPS Module Information (Packing Dimension)
UPS
[kVA]
Width
[in. (mm)]
Depth
[in. (mm)]
Height
[in. (mm)]
Gross Weight
[lbs. (kg)]
500
79
(1,990)
41
(1,020)
88
(2,220)
3090
(1,400)
750
89
(2,260)
41
(1,030)
88
(2,220)
4,375
(1,970)
Table 3-4
UPS Module Efficiency
UPS
[kVA]
Percent of Full Load
25%
50%
75%
100%
500
97.9%
98.2%
98.0%
97.6%
750
95.8%
98.0%
97.9%
97.5%