48
G2020 Series UPS Installation and Operation Manual
– 94861-004
IFAU-09
CN99
CN98
TLBIN
ON
TLAIN
TN1
IOAU-09
5
6
AC
OUTPUT
UPS-1
A
B
C
UPS-1
A
B
C
UPS-2
AC OUTPUT
47
48
49
50
52L1-AX
52L2-AX
Toshiba Tie Cabinet (TTC)
A50
B50
C50
CN97
CN96
TLBOUT
TLAOUT
CN954
CN953
CB2IN
CB1IN
CN952
CN951
CA2IN
CA1IN
CN944
CN943
CB2OUT
CB1OUT
CN942
CN941
CA2OUT
CA1OUT
ON
IFAU-09
CN99
CN98
TLBIN
ON
TLAIN
TN1
IOAU-09
5
6
AC
OUTPUT
UPS-2
A50
B50
C50
CN97
CN96
TLBOUT
TLAOUT
CN954
CN953
CB2IN
CB1IN
CN952
CN951
CA2IN
CA1IN
CN944
CN943
CB2OUT
CB1OUT
CN942
CN941
CA2OUT
CA1OUT
ON
*1
*2
*2
*2
*2
*1
Figure 5-6 Diagram of Power & Control Wire Connections for 2 units in MMS Configuration
NOTE
TLAx and TLBx are redundant signal
lines. CAx and CBx are redundant
signal lines.
Redundant lines provide reduced
vulnerability to cable damage when
TLAx/CAx circuits are installed in
separate conduit from TLBx/CBx
circuits.
NOTE
!
Use Ethernet STP (Shielded
Twisted Pair) Cable (Cat 5 or better)
with shielded RJ45 modular
connectors for all communication
cabling.
Use of UTP (Unshielded Twisted Pair)
Cable may cause malfunction.
NOTE
!
Total cable length from UPS-1
to UPS-2 should be within 100m.
*1
Return from the last
UPS module to the first UPS
module (continuous loop).
*2
DIP switch position
UPS-1 and UPS-2: ON
Power
Cabling
Signal
Cabling
Communication
Cabling