manualshive.com logo in svg
background image

           

Instruction Manual 

        

        Pure Sine Wave Inverter UPS      

  (3 IN 1 Inverter)

Содержание YXP-1000-UPS

Страница 1: ...Instruction Manual Pure Sine Wave Inverter UPS 3 IN 1 Inverter ...

Страница 2: ...y and Saving Mode 5 4 1 Initial State 5 5 Protection 5 5 1 Input Protection 5 5 2 Output Protection 6 5 3 Failure Message Guidelines 7 6 Installation Wiring 7 6 1 Wiring for Batteries 7 6 2 Suggested Battery Bank Capacity 8 6 3 Requirement of Installation 8 6 4 Mounting Suggestion 8 6 5 Derating 9 7 Failure Correction Notes 9 10 8 Installation Diagram 10 9 Warranty 10 ...

Страница 3: ...and model number in one battery bank Using batteries from different manufacturers or different capacity is strictly prohibited Never allow a spark or flame in the vicinity of the batteries because it may generate explosive gases during normal operation Make sure the air flow from the fan is not obstructed at both sides front and back of the inverter Please allow at least 15cm of space Please do no...

Страница 4: ...charger When utility is disconnected the inverter will switch back to inverting from the batteries without disrupting the power going to the appliances This is usually very quick less than 35ms Battery Priority when inverter output is available output as invertering is priority When inverter output is unavailable this unit will transfer to utility the utility supply AC to equipments transfer time ...

Страница 5: ...ly converting inverter time 35ms Efficiency up to 92 Input Voltage 12V 24V 48V 72V 96V 110V Output Voltage 100V 110V 115V 120V 220V 230V 240V Frequency 50Hz 60Hz Protection Function Low voltage shutdown protection Over input voltage protection Over temperature protection Over load protection Short circuit protection Reverse polarity protection Fuse Internal or external Battery type Open Sealed Lea...

Страница 6: ...m GND connect a copper wire between the grounding terminal on the inverter charger and the earth grounding system or vehicle chassis Ventilation outlet To decrease the temperature of the inverter LED Indicator Light Utility Charging Inverter Fault a Utility When connecting the utility the light turns green b Charging When charging the light turns red once battery was fully charged the light will t...

Страница 7: ...tate is 230Vac 50Hz or 110Vac 60Hz Setting standby saving mode unused 5 Protection 5 1 Input Protection Battery Reversed Polarity Protection If the battery input is connected in reverse polarity the internal or external fuse of the inverter would blow and the inverter should be send back FACTORY for repair For the inverter with external fuse there is the spare fuse in the box Please disclose the f...

Страница 8: ...sounded 5 times continuous alarm and the fault light turns red at the same time When the internal temperature drops to 45 degrees the inverte will automatically return to normal status AC Output Abnormal Protection When the AC output voltage of the inverter is too high or too low the unit will turn off and should be restarted again AC Output Short Circuit Protection When a short circuit situation ...

Страница 9: ...the internal temperature is too high Buzzer alarm is sounded continuousl y Overload protection The inverter will shut down after 5S and then restarts automatically after another 5S waiting continuous loop 6 Installation Wiring 6 1 Wiring for Batteries Wire connections should be as short as possible and less than 1 5 meter is highly recommended Make sure that suitable wires are chosen based on the ...

Страница 10: ... time battery capacity 40Ah battery could meet the discharge time of 85 minutes Note Actual discharge time error may exist according to the lifespan and mantainenece of the battery 6 3 Requirement of Installation The unit should be mounted on a flat surface or holding rack with suitable strenth In order to ensure the lifespan of the unit please refrain from operating in environment of high dust hi...

Страница 11: ...r may not start up successfully with these kinds of load When the output are capacitive or rectified equipments such as switching power supply it is suggested to operate these equipment at no load or light load To ensure proper operation you should increase the load only after the inverter has started up 7 Failure Correct Notes The inverter should be serviced by a professional technician Any impor...

Страница 12: ...loaded or shout circuited Discharging period of batteries is too short Batteries are aged or broken Replace the batteries Battery capacity is too small Reconfirm the specification and enlarge the battery capacity as suggested Fan does not spin Clog with foreign bodies Remove the foreign objects Malfunction of the fan Repaire required Please send it back to us or any of our distributors 8 Installat...

Отзывы: