background image

 

 

Operating instructions 

Uninterruptible Power Supply ECP-024 

 

 

 

Emerson Climate Technologies GmbH  

www.climate.emerson.com/en-gb

  

Date: 27.08.2020

 

Am Borsigturm 31 I 13507 Berlin I Germany 

 

ECP_OI_EN_DE_FR_ES_IT_RU_0820_R07_863031.docx 

G e n e r a l   i n fo r ma t i o n : 

ECP-024 is intended to be used with EMERSON’s EXD-U01/U02 Universal Driver 

Module and/or EXD-SH1/2 Stand Alone Superheat controller. 

In case of power failure, ECP-024 insures that the valve is driven to the shut-off 

position. ECP-024 can be connected to two EXD-… 

  S a f e ty   i n s tr u c t i o n s : 

 

Read operating instructions thoroughly. Failure to comply can result in device 

failure, system damage or personal injury. 

 

According to EN 13313 it is  intended for use by persons having the 

appropriate knowledge and skill. 

 

Do not exceed the specified maximum ratings for temperature, voltage and 

current. 

 

Before installation or service disconnect all voltages from system and device. 

 

Ensure that design, installation and operation are according to European and 

national standards/regulations.  

 

Do not operate system before all cable connections are completed. 

 

Disposal: ECP-024 contains lead acid gel rechargeable battery Electrical and 

electronic waste must NOT be disposed of with other commercial waste. 

Instead, it is the user responsibility to pass it to a designated collection point 

for the safe recycling of Waste Electrical and Electronic Equipment (WEEE 

directive 2012/19/EU). For further information, contact your local 

environmental recycling center. 

M o u n t i n g   l o c a t i o n   /   I n s t a l l a t i o n : 

 

Protect ECP-024 against sunrays, heat and moisture. 

 

It is intended for installation in electrical switch 

board/cabinet/box.  

 

On vertical walls, with output connectors on top 

side. 

 

ECP-024 is delivered with bracket suitable for 

mounting on DIN-Rail. Hang device above DIN-

Rail and push down-  and backward until it snaps 

completely and hold by DIN-Rail.  

 

Fig.1:

 

 

ECP-024

 

 

Ventilation of electrical switch board/ cabinet /box 

(natural or forced) is recommended in order to 

reduce temperatures and consequently not to reduce 

the life expectancy of the battery. 

 

Electrical Terminals K09-P00 (Part No. 804560) are 

required. 

 

Fig.2

 

K09-P00  

(Part No. 804560)

 

W i r i n g : ( s e e  Fi g . 3 ) 

 

It is mandatory the external grounding backside of ECP-024. (see Fig.1) 

 

Use a class II category transformer for 24 VAC power supply. Do not ground the 

24 VAC line. 

 

See also operating instruction of Emerson EXD-U... and EXD-SH1/2. 

 

It is recommended to supply the ECP-024 from same source (e.g. transformer) as 

the connected driver/controller. 

 

Recommended wire size Ø 0.5…2.5 mm

2

S e r v i c e :  

 

It is recommended that ECP-024 to be checked for proper function and life of 

rechargeable batteries during regular system inspection. It is advisable to add the 

following procedure to the service handbook of system/unit. 

T e s t  o f   b a t t e r y   h e a l t h : 

 

Disconnect the wires from ECP-024. 

 

Connect a standard 22 

 resistor with minimum 15 W capacity to one of output 

power and a DC-voltmeter as shown in Fig. 4.  

 

Apply supply voltage 24 VAC to ECP-024 and measure the output power voltage. 

It should be approximately 18.5 VDC. 

 

Disconnect the supply voltage 24 VAC from ECP-024  and watch the output 

voltage. Power output must maintain at 18 VDC for minimum 5 seconds. 

 

ECP-024 always interrupts power output after 15 seconds when the supply voltage 

24 VAC is disconnected. 

B a t t e r y   r e pl a c e m e n t   i n s t r u c t i o n : 

 

In case of battery life end, follow the following procedures for replacement of both 

batteries at the same time: 

1.

 

Disconnect the power and pull all green terminals from housing. 

2.

 

Unscrew both black plastics covers with star-key T-10 and remove them. (Fig. 5) 

3.

 

Pull out carefully the electronic board from right side. (Fig. 6) 

4.

 

Disconnect the connectors of each battery from the electronic board and remove 

the soft dividing plate as well as both old batteries from the housing (Fig. 7) 

5.

 

Place carefully the new batteries inside of the housing, in the same position and 

insert the soft dividing plate after batteries. (Fig. 8) 

6.

 

Connect the new batteries to the electronic board (Fig. 9) 

7.

 

The electronic board must be inserted in  the two internal slots of housing 

(Fig. 10).  

8.

 

Put back the cover plates, press them firmly to their place and tighten with screws 

Ensure, that the small grey soft pads are placed correctly in the middle of the 

black cover plates. (Fig. 11) Then connect all previously removed terminals and 

attach by sticker the date of battery change. 

9.

 

Check the functionality of ECP-024 device like under point “

Test of battery 

health”.

 

T e c h ni c a l   D a ta :    

Supply voltage 

24 VAC 

±

 10% 

Number of power outputs 

Two, each approx. 18 VDC 

Number of internal batteries 

Two pieces 

Type of internal battery 

Lead gel rechargeable battery,  

12 VDC / 0.8 Ah 

Charging time 

less than two hours 

Ambient temperature 

1…25 °C for optimum battery life time  

> 35 °C lifetime of battery is maximum 2 years 

Electronic board temperature 

0…+65 °C 

Markings 

 according to EMC directive 

 

Dimensions 

 

 

 

 

 

Summary of Contents for ECP-024

Page 1: ...ing instruction of Emerson EXD U and EXD SH1 2 It is recommended to supply the ECP 024 from same source e g transformer as the connected driver controller Recommended wire size Ø 0 5 2 5 mm2 Se r vi ce It is recommended that ECP 024 to be checked for proper function and life of rechargeable batteries during regular system inspection It is advisable to add the following procedure to the service han...

Page 2: ...erden Siehe auch die Bedienungsanleitung von Emerson EXD U und EXD SH1 2 Es wird empfohlen ECP 024 aus derselben Spannungsquelle z B Transformator wie der angeschlossene Treiber Controller zu versorgen Empfohlener Kabelquerschnitt Ø 0 5 2 5 mm2 Se r vi ce Bei jeder Anlagenwartung Funktion des ECP 024 und der Akkus prüfen Dazu diese Anleitung dem Anlagen Servicehandbuch beilegen T e st des Ba tte r...

Page 3: ...XD U et EXD SH1 2 Il est recommandé d alimenter ECP 024 par la même source ex transformateur que le régulateur à protéger Taille recommandée des câbles Ø 0 5 2 5 mm2 Se r vi ce Il est recommandé de contrôler le bon fonctionnement de ECP 024 et l état des batteries rechargeables pendant les inspections régulières des installations Il est conseillé d ajouter la procédure suivante au manuel de mainte...

Page 4: ... Se recomienda suministrar el ECP 024 desde la misma fuente por ejemplo transformador que el controlador controlador conectado Sección de cable recomendada Ø 0 5 2 5 mm2 Se r vi ci o Se recomienda que ECP 024 sea revisado para verificar que las baterías recargables funcionen correctamente y duren durante la inspección regular del sistema Es aconsejable agregar el siguiente procedimiento al manual ...

Page 5: ...ei driver Emerson EXD U e EXD SH1 2 Si raccomanda di utilizzare per l ECP 024 la stessa alimentazione del driver controllore ad es il trasformatore Dimensioni consigliate dei conduttori Ø 0 5 2 5 mm2 Ma nute nzi o ne Durante la regolare ispezione del sistema si raccomanda di controllare il corretto funzionamento e la durata delle batterie ricaricabili dell ECP 024 Si consiglia di aggiungere la seg...

Page 6: ...рансформаторы II класса Не заземляйте питающие кабели 24 В перем тока Смотри инструкцию контроллера EXD Рекомендуется запитывать ECP 024 fот того же источника трансформатора что и привод контроллер Рекомендуемый размер проводов Ø 0 5 2 5 мм2 Т ех ни че ск ое о бс лу жи ва ни е Рекомендуется проверять фукционал ECP 024 и срок службы аккумуляторных батарей во время регулярного осмотра системы Рекоме...

Page 7: ... www climate emerson com en gb Date 27 08 2020 Am Borsigturm 31 I 13507 Berlin I Germany ECP_OI_EN_DE_FR_ES_IT_RU_0820_R07_863031 docx Fig Pис 3 EXD U EXD SH1 2 Fig Pис 4 Fig Pис 5 Fig Pис 6 Fig Pис 7 Fig Pис 8 Fig Pис 9 Fig Pис 10 Fig Pис 11 ...

Reviews: