Chapter 3 System Construction
6F8C1625
20
3
3.6 Startup Procedure
There are the following two modes for I/O module input/output operations:
(1) FL654A recognizes the I/O module composition when the power supply is turned on, and
FL654A executes the input/output operation by this module composition. (AUTO)
(2) After confirming the I/O module composition when the power supply is turned on, the user
saves the I/O module composition in non-volatile memory in FL654A. FL654A executes the
input/output operation according to the saved I/O module composition. (CONF/LOCK)
In the mode in (1), if any I/O module is defective at power-ON, I/O module configuration information
is created excluding such I/O module. Thus there is a possibility of disagreement in correspondence
between the common memory and the slots into which I/O modules have been installed. It is
recommended that I/O module input/output be performed on the basis of the information saved in
the non-volatile memory, i.e., in the mode in (2).
3.6.1 CONF/LOCK Designation Startup
Begin
(i) Install the power, expansion, FL654A, and I/O
modules in the base unit. When the expansion unit
is used, connect an expansion cable.
(v) Connect the communication cable.
(vi) Turn ON the power.
Start up
After that, I/O module input/output is
automatically performed based on the saved
I/O information when power is turned ON in
this condition.
FL654A switch settings in step (i)
・
Node address: Depends on the system.
・
Talker block head and listener block head:
Depends on the system.
・
RUN/HALT switch: HALT
・
Operation setting switch:
Ethernet setting:
Set according to the system.
Generally, auto-negotiation is set.
I/O composition setting: CONF
I/O status setting in down mode:
Depends on the system.
(ii) Turn ON the power (the FL654A automatically
recognizes the connected I/O modules).
(iii) Connect a PC to the TOOL connection port
and check I/O module connections using terminal
software.
(iv) After checking I/O module connections, once
turn OFF the power and return the FL654A switch
settings to ordinary usage condition.
For more information on check in step (iii),
see Chapter 5.
FL654A settings in step (iv) (settings to be
changed)
・
RUN/HALT switch: RUN
・
Operation setting switch:
I/O composition setting: LOCK
Figure 3-3 CONF/LOCK designation startup procedure
Содержание FL654A
Страница 1: ...Unified Controller nv Series FL net Remote I O Station Module FL654A User s Manual 6F8C1625 ...
Страница 16: ...6F8C1625 xiv ...
Страница 38: ...Chapter 3 System Construction 6F8C1625 22 3 ...
Страница 48: ...Chapter 5 I O configuration information 6F8C1625 32 5 ...
Страница 88: ...Chapter 8 Startup Using nV Tool 6F8C1625 72 8 ...
Страница 98: ...Chapter 9 Maintenance Using nV Tool 6F8C1625 82 9 ...
Страница 101: ...85 A 85 Appendix A Specifications A 1 General specifications 86 A 2 FL654A module specifications 87 ...
Страница 105: ...B 89 Appendix B Outside Dimensions ...
Страница 107: ...C 91 Appendix C Accessories and Related Products C 1 Accessories 92 C 2 Related Products 93 ...
Страница 110: ...Appendix C Accessories and Related Products 6F8C1625 94 C ...
Страница 111: ...D 95 Appendix D Decimal hexadecimal Conversion Table ...
Страница 114: ...Appendix D Decimal hexadecimal Conversion Table 6F8C1625 98 D ...
Страница 116: ...1625 1 1810 ...