A.2 FL654A module specifications
Unified Controller nv Series FL-net Remote I/O Station Module FL654A User's Manual
87
A
A.2 FL654A module specifications
Table A-2
FL654A module specifications
Item
Specification
Remark
Transmission
specifications
*1
Transmission
standards
Compliant with FA control network [FL-net]
protocol version 3.01 class 1.
(equivalent to version 2.00)
The standard noted at the left
conforms to JIS B 3521 of the
Japanese Industrial Standards.
Transmission rate
10Mbps / 100Mbps
Electrical interface
IEC68802.3 (CSMA/CD compliant)
Transmission
protocol
FA link protocol (version 3.01 class 1)
UDP/IP
Number of
connectable units
254 units maximum
Connection
connector
10BASE-T / 100BASE-TX
I/O module
connection
I/O module type
G2 I/O modules
For connectable I/O module
types, see Table A-3.
Number of
connectable
modules
32 modules maximum
I/O module-
updating intervals
Updated every 25 ms
(when 32 modules are installed)
Setting
Assignment of I/O data to common memory
data --- automatic setting or setup from the
integrated controller nV-Tool.
The common memory allows selection of
Area 1 or Area 2.
Communications
service
Cyclic
transmission
*2
Capacity: 8K words + 8K bits
Transmission performance:
50 ms or less / 32 units
For 2K words + 2K bits
When 32 units are mounted
Send: 256 + 4 words maximum
Receive: 128 words maximum
Message
transmission
FL-net message transmission support
1 to 1 transmission / 1 to N transmission
1024 bytes maximum
Dimensions
G2 I/O module size. Single slot width.
130(H)x35(W)x105(D)mm
Not including projections
Operating voltage range
DC power supply (5 Vdc ± 10%)
Current consumption
800mA or less at 5Vdc
Weight
250g or less
*1 Transmission specifications compliance to FL-net protocol version 3.01 class 1 (equivalent to
version 2.00). It does not correspond to FL-net protocol version 1.00.
*2 This transmission performance is the initial target performance of FL-net. To achieve this, each
transmission station must transmit data and receive and send the token within approx. 1.56 ms
after receiving the token.
Important
・
The FL654A is applied to systems within the range of cyclic transmission performance according
to FL-net standard.
Содержание FL654A
Страница 1: ...Unified Controller nv Series FL net Remote I O Station Module FL654A User s Manual 6F8C1625 ...
Страница 16: ...6F8C1625 xiv ...
Страница 38: ...Chapter 3 System Construction 6F8C1625 22 3 ...
Страница 48: ...Chapter 5 I O configuration information 6F8C1625 32 5 ...
Страница 88: ...Chapter 8 Startup Using nV Tool 6F8C1625 72 8 ...
Страница 98: ...Chapter 9 Maintenance Using nV Tool 6F8C1625 82 9 ...
Страница 101: ...85 A 85 Appendix A Specifications A 1 General specifications 86 A 2 FL654A module specifications 87 ...
Страница 105: ...B 89 Appendix B Outside Dimensions ...
Страница 107: ...C 91 Appendix C Accessories and Related Products C 1 Accessories 92 C 2 Related Products 93 ...
Страница 110: ...Appendix C Accessories and Related Products 6F8C1625 94 C ...
Страница 111: ...D 95 Appendix D Decimal hexadecimal Conversion Table ...
Страница 114: ...Appendix D Decimal hexadecimal Conversion Table 6F8C1625 98 D ...
Страница 116: ...1625 1 1810 ...