Chapter 7 RAS Function
6F8C1625
44
7
Contents
Table 7-3 Node status
Status
Contents
mode
The state of the FL654A is displayed.
RUN … Join in the network, and the I/O operation is executed
STBY … Join in the network, and the I/O operation is stopped
DOWN … Down mode
message
Display of enable / disable for message data transmission
cyclic
Display of enable / disable for cyclic data transmission
LNK
Display of join in (ON) / leave from (OFF) the network
ERR
Display of abnormality (ON) / normality (OFF) of the parameter
PVERR
Display of the protocol version disagreement
Detection (ON) / No detection (OFF)
GDLNK
Display of the result of the transmission line link test
Normality (ON) / Abnormality (OFF)
DPADR
Display of the detection of duplicated node number
Detected (ON) / Not detected (OFF)
TEST
Always turning off
When FL654A is down mode, the down code is displayed under "mode".
Table 7-4 Down code
Down code
Description
0x0000
NMI occurrence
NMI occurred due to unknown cause
0x0010
External WDT error
NMI occurred due to an external WDT.
0x0020
Bus stall
NMI occurred due to bus stall.
0x0030
Occurrence of general
exception
Occurrence of general exception
0x0160
ROM area check failure
Error was detected by FROM’s BCC check at initialization.
0x0260
RAM area check failure
Error was detected by RAM check at initialization.
0x0261
Program area check failure
Error was detected by BCC check on the SRAM program area at
initialization or during operation.
0x0600
Detection of a duplicated
node number
A duplicated node number was detected at sign-up to the network.
0x0601
FL-network sign-up failure
An FL network sign-up failure was detected.
0x0700
Node number setting error
The node address switch has been incorrectly set. (0x00, 0xFF)
0x0800
Protocol version
disagreement
Disagreement of the FA link protocol version was detected.
0x0900
Format error
An FA link protocol parameter was detected to be wrong. (Detection of
test operation only)
0x0A01
Ethernet setting failure
Ethernet setting (operation setting switch bits 1 and 2) was detected to
be faulty.
0x0A03
I/O configuration information
setting failure
Setting of I/O configuration information (operation setting switch bits 3
and/or 4) was detected to be incorrect.
0x0A04
I/O configuration information
abnormality
The information saved in FRAM does not match the actual mounting
status, I/O module status, type, number of I/O points. Or, the status is an
abnormal value.
0x0A05
I/O configuration information
not saved
I/O configuration information is not stored in FRAM
0x0A06
Failure to save I/O
configuration information
I/O configuration information can not be stored in FRAM
0x0A07
Common memory area
allocation error
I/O can not be allocated to common memory area
Содержание FL654A
Страница 1: ...Unified Controller nv Series FL net Remote I O Station Module FL654A User s Manual 6F8C1625 ...
Страница 16: ...6F8C1625 xiv ...
Страница 38: ...Chapter 3 System Construction 6F8C1625 22 3 ...
Страница 48: ...Chapter 5 I O configuration information 6F8C1625 32 5 ...
Страница 88: ...Chapter 8 Startup Using nV Tool 6F8C1625 72 8 ...
Страница 98: ...Chapter 9 Maintenance Using nV Tool 6F8C1625 82 9 ...
Страница 101: ...85 A 85 Appendix A Specifications A 1 General specifications 86 A 2 FL654A module specifications 87 ...
Страница 105: ...B 89 Appendix B Outside Dimensions ...
Страница 107: ...C 91 Appendix C Accessories and Related Products C 1 Accessories 92 C 2 Related Products 93 ...
Страница 110: ...Appendix C Accessories and Related Products 6F8C1625 94 C ...
Страница 111: ...D 95 Appendix D Decimal hexadecimal Conversion Table ...
Страница 114: ...Appendix D Decimal hexadecimal Conversion Table 6F8C1625 98 D ...
Страница 116: ...1625 1 1810 ...