8.2 Remote I/O Startup Procedure
Unified Controller nv Series FL-net Remote I/O Station Module FL654A User's Manual
69
8
8.2.7 Download
Download the I/O configuration information using nV-Tool. There are the following two methods for
downloading I/O configuration information.
(1) Local connection
Directly connect nV-Tool to the TOOL connection connector in the FL654A that is the target for
download.
(2) Remote connection
Connect nV-Tool to the TOOL connection connector of an FL654A that is not the target for
download. (For remote connection, set the timeout time of the transmission parameter setting
to 10 seconds or more.)
8.2.8 Starting the Module
(1) DIP switch setting
Set the operation setting switch of the FL654A so that SW3 is ON and SW4 is OFF.
(2) Set the RUN/HALT switch to RUN.
(3) Turn ON the power.
Содержание FL654A
Страница 1: ...Unified Controller nv Series FL net Remote I O Station Module FL654A User s Manual 6F8C1625 ...
Страница 16: ...6F8C1625 xiv ...
Страница 38: ...Chapter 3 System Construction 6F8C1625 22 3 ...
Страница 48: ...Chapter 5 I O configuration information 6F8C1625 32 5 ...
Страница 88: ...Chapter 8 Startup Using nV Tool 6F8C1625 72 8 ...
Страница 98: ...Chapter 9 Maintenance Using nV Tool 6F8C1625 82 9 ...
Страница 101: ...85 A 85 Appendix A Specifications A 1 General specifications 86 A 2 FL654A module specifications 87 ...
Страница 105: ...B 89 Appendix B Outside Dimensions ...
Страница 107: ...C 91 Appendix C Accessories and Related Products C 1 Accessories 92 C 2 Related Products 93 ...
Страница 110: ...Appendix C Accessories and Related Products 6F8C1625 94 C ...
Страница 111: ...D 95 Appendix D Decimal hexadecimal Conversion Table ...
Страница 114: ...Appendix D Decimal hexadecimal Conversion Table 6F8C1625 98 D ...
Страница 116: ...1625 1 1810 ...