4400 Series Installation and Operation Manual – 64527-008
9.4 Power Terminal Blocks and Cable Sizing
Note: Always consult your site specific, local, state, and NEC electrical codes for wiring, cabling, and circuit protection
device requirements.
NOTICE
The Power Lugs for the 15-100kVA UPS are not designed for use with high-flex/locomotive-
type DLO cabling.
Use of these conductors may lead to conductor strand breakage effectively reducing the
current carrying capacity of the conductor.
The terminal blocks for the 15-30 kVA UPS are shown in Figure 9.5.
Use only copper wires for external cables. See Appendix D for alternate voltage and cabling configurations.
TABLE 9.1: RECOMMENDED MINIMUM CABLE SIZE & TIGHTENING TORQUE FOR 15-30KVA UPS FOR 120/208V IN,
120/208V OUT
Block Number
Cable Size (Min-Max) 75 °C Copper Wire in Conduit
Tightening Torque
Terminal Lug
Capacity (AWG)
15 kVA
(AWG)
20 kVA
(AWG)
25 kVA
(AWG)
30 kVA
(AWG)
AC Input A, B, C
#12 – #2
#4
#2
#2
#2
35-44 in-lb
(4-5 N•m)
(6.5 x 1.2 mm Flat blade
screwdriver)
AC Input Neutral (N)
2
#12 – #2
#2
#2
#2
#2
AC Output A, B, C
#12 – #2
#6
#3
#2
#2
AC Output Neutral (N)
2
#12 – #2
#2
#2
#2
#2
Secondary Input A, B, C
#12 – #2
#6
#3
#3
#2
Secondary Neutral (N)
2
#12 – #2
#2
#2
#2
#2
Battery Ter/-
1
#12 – #2
#2
#2
#2
#2
1
One battery string. (Consult factory if using more than one battery string.)
2
Size neutral cable appropriate to actual load type: balanced, unbalanced, non-linear.
3
No more than 3 conductors per conduit for these sizing recommendations.
Use only copper wires for external cables.
TABLE 9.2: RECOMMENDED MINIMUM CABLE SIZE & TIGHTENING TORQUE FOR 50KVA UPS FOR 120/208V IN,
120/208V OUT
Block Number
Cable Size (Min-Max) 75 °C Copper Wire in Conduit
Tightening Torque
2
Terminal Lug Capacity
50 kVA
AC Input A, B, C
#6 – 250 kcmil
4/0
225-250 in-lb
(25.4-28.2 N•m)
(Hex drive socket)
AC Input Neutral (N)
2
#6 – 250 kcmil
250 kcmil
AC Output A, B, C
#6 – 250 kcmil
4/0
AC Output Neutral (N)
2
#6 – 250 kcmil
250 kcmil
Secondary Input A, B, C
#6 – 250 kcmil
4/0
Secondary Neutral (N)
2
#6 – 250 kcmil
250 kcmil
Battery Ter/-
1
#6 – 250 kcmil
250 kcmil
1
One battery string. (Consult factory if using more than one battery string.)
2
Size neutral cable appropriate to actual load type: balanced, unbalanced, non-linear.
Use only copper wires for external cables.
Содержание 4400 Series
Страница 2: ......
Страница 6: ...This page left intentionally blank ...
Страница 10: ...This page left intentionally blank ...
Страница 114: ...104 4400 Series Installation and Operation Manual 64527 008 This Page Intentionally Left Blank ...
Страница 117: ...107 4400 Series Installation and Operation Manual 64527 008 FIGURE A 3 4400 50 KVA PHYSICAL DIMENSIONS 1 2 ...
Страница 118: ...108 4400 Series Installation and Operation Manual 64527 008 FIGURE A 4 4400 50 KVA PHYSICAL DIMENSIONS 2 2 ...
Страница 119: ...109 4400 Series Installation and Operation Manual 64527 008 FIGURE A 5 4400 80 KVA PHYSICAL DIMENSIONS ...
Страница 120: ...110 4400 Series Installation and Operation Manual 64527 008 FIGURE A 6 4400 100 KVA PHYSICAL DIMENSIONS ...
Страница 136: ...This page left intentionally blank ...
Страница 137: ......