19
4400 Series Installation and Operation Manual – 64527-008
6 Storage/Operating Environment
6.1 Storage Environment
Observe the following when storing the UPS.
•
Store UPS indoors.
•
Maximum storage time for the UPS between powered operation cycles is three years. If the UPS has been stored
for a period exceeding 36 months, contact your factory authorized representative of guidance in starting the unit.
•
Temperature fluctuations should be minimized.
•
The optimal storage temperature range is 68 – 77 °F (20 – 25° C).
•
A maximum temperature range of 32 – 104 °F (0 – 40 °C) should be observed.
•
The optimal relative humidity at the storage location should be between 50 – 60%.
•
Humidity must not exceed 90%.
•
Avoid locations where UPS may be exposed to corrosive gas.
•
Avoid locations with dirt and/or dust.
TABLE 6.1: UPS STORAGE/OPERATING ENVIRONMENT STANDARDS
Item
Environment standard
Storage Location
Indoors
Ambient Temperature
Minimum storage temperature: 32 °F (0 °C)
Maximum storage temperature: 104 °F (40 °C)
Relative Humidity
The relative humidity must be between 30 and 90% and without
condensation due to temperature changes.
Altitude
This equipment is rated for installations up to 3240 ft. (1000 m) above sea level.
Consult with the factory to determine the derating factor for installations above 3240
ft. (1000 m).
Dust
Dust must not exceed normal atmospheric levels and must not
include conductive particles, silicone or oils.
Flammable Gas
No flammable and/or explosive gas.
Hydrogen sulfide (H
2
S)
Less than or equal to 0.0001 PPM
Sulfurous acid gas (SO
2
)
Less than or equal to 0.05 PPM
Chlorine gas (Cl
2
)
Less than or equal to 0.002 PPM
Ammonia gas (NH
3
)
Less than or equal to 0.1 PPM
Nitrous acid gas (NO
2
)
Less than or equal to 0.02 PPM
Nitrous oxides (NOx)
Less than or equal to 0.02 PPM
Ozone (O
3
)
Less than or equal to 0.002 PPM
Hydrochloric acid mist (HCl) Less than or equal to 0.1 mg/m
3
6.2 Precautions
Initial startup/commissioning of the UPS should be performed by factory authorized personnel.
1. The UPS should not be powered up until the entire operation manual has been read.
2. The voltage of the input power source must be within the rated input voltage range. The input frequency range
must be within the rated input frequency range.
Содержание 4400 Series
Страница 2: ......
Страница 6: ...This page left intentionally blank ...
Страница 10: ...This page left intentionally blank ...
Страница 114: ...104 4400 Series Installation and Operation Manual 64527 008 This Page Intentionally Left Blank ...
Страница 117: ...107 4400 Series Installation and Operation Manual 64527 008 FIGURE A 3 4400 50 KVA PHYSICAL DIMENSIONS 1 2 ...
Страница 118: ...108 4400 Series Installation and Operation Manual 64527 008 FIGURE A 4 4400 50 KVA PHYSICAL DIMENSIONS 2 2 ...
Страница 119: ...109 4400 Series Installation and Operation Manual 64527 008 FIGURE A 5 4400 80 KVA PHYSICAL DIMENSIONS ...
Страница 120: ...110 4400 Series Installation and Operation Manual 64527 008 FIGURE A 6 4400 100 KVA PHYSICAL DIMENSIONS ...
Страница 136: ...This page left intentionally blank ...
Страница 137: ......