4400 Series Installation and Operation Manual – 64527-008
11.8
50–100kVA Specifications – w/ External
Battery Backup
4400 SPECIFICATIONS: 50–100kVA w/ External Battery Backup
Specification
50kVA
80kVA
100kVA
GENERAL
Model Number
4400X3X500XA
4400X3X800XA
4400F3F10KXA
Capacity Output
50kVA (45kW)
80 kVA (72kW)
100kVA (90kW)
Topology
Double conversion all-IGBT UPS
INPUT
Voltage (V)
Nominal (Xfmr.) Input V10% to -15% (Intermittently to -30% at 70% load
1
), 3P/4W
+GND or 3P/3W + GND
100kVA: +10% to -10% only
Key
Transformer Voltage
Key
Transformer Voltage
A
200V Iso Xfmr
M
380V Iso Xfmr
B
208V Iso Xfmr
N
400V Iso Xfmr
C
220V Iso Xfmr
P
415V Iso Xfmr
D
230V Iso Xfmr
Q
230/133V Auto-Xfmr
E
240V Iso Xfmr
R
240/139V Auto-Xfmr
F
208/120V (No Xfmr)
S
480V Iso Xfmr
G
220/127V Auto-Xfmr
T
(Undefined)
H
380/220V Auto-Xfmr
U
600/347V Auto-Xfmr
I
400/230V Auto-Xfmr
V
600V Iso Xfmr
J
415/240V Auto-Xfmr
X
Not Used
K
480/277V Auto-Xfmr
Z
200/115V Auto-Xfmr
Current (Nominal) (A)
140 A
224 A
278 A
Current (Max) (A)
173 A
278 A
347 A
Current Limit (%)
125% of Rated load
Current THD (%)
< 5%
Frequency (Hz) [and range]
50/60 Hz ± 5 Hz
Input Power Factor (PF) @ full load
>0.98
Walk-in Function (sec)
20% to 100% over 3, 5, or 9 sec. (Selectable)
Cold Start (0-100% load) (sec)
25 sec. from cold start
BYPASS
Voltage (V)
Nominal
Output Voltage, 3P/4W +GND or 3P/3W + GND
See Input Voltage Transformer Key
Frequency (Hz)
50/60 Hz ±5%
Bypass Overload @ 125% Load
10 min. @ 125% Load
Bypass Overload @ 150% Load
2 min. @ 150% Load
Bypass Overload @ 1000% Load
1 cycle @ 1000% Load
Automatic Retransfer (Max load % for
Retransfer)
Yes
1 - Requires adjustment of factory/service adjustable parameters.
Содержание 4400 Series
Страница 2: ......
Страница 6: ...This page left intentionally blank ...
Страница 10: ...This page left intentionally blank ...
Страница 114: ...104 4400 Series Installation and Operation Manual 64527 008 This Page Intentionally Left Blank ...
Страница 117: ...107 4400 Series Installation and Operation Manual 64527 008 FIGURE A 3 4400 50 KVA PHYSICAL DIMENSIONS 1 2 ...
Страница 118: ...108 4400 Series Installation and Operation Manual 64527 008 FIGURE A 4 4400 50 KVA PHYSICAL DIMENSIONS 2 2 ...
Страница 119: ...109 4400 Series Installation and Operation Manual 64527 008 FIGURE A 5 4400 80 KVA PHYSICAL DIMENSIONS ...
Страница 120: ...110 4400 Series Installation and Operation Manual 64527 008 FIGURE A 6 4400 100 KVA PHYSICAL DIMENSIONS ...
Страница 136: ...This page left intentionally blank ...
Страница 137: ......