89
4400 Series Installation and Operation Manual – 64527-008
12.17 Setup: Calibrating the Touchscreen
At anytime while using the tabs to view system details, the touchscreen can be calibrated by executing the built-in
calibration routine.
To calibrate the touchscreen:
1.
Press the
Setup
Tab.
2.
Press the
DISP-EX 800
button.
3.
Press the entry
Cali
(
Parameter 8211)
to begin the calibration routine.
4.
Follow the directions on the display to
press the “+” at each location it flashes
on the display. To exit the calibration
routine press QUIT at any time.
See Fig. 12-15 A, B.
5.
After the touchscreen has been recalibrated
the display will indicate that the calibration
routine has passed. Press Quit to return
to the main display. See Fig. 12-15 C.
FIGURE 12.15: TOUCHSCREEN DIS-
PLAY CALIBRATION
A
B
C
Содержание 4400 Series
Страница 2: ......
Страница 6: ...This page left intentionally blank ...
Страница 10: ...This page left intentionally blank ...
Страница 114: ...104 4400 Series Installation and Operation Manual 64527 008 This Page Intentionally Left Blank ...
Страница 117: ...107 4400 Series Installation and Operation Manual 64527 008 FIGURE A 3 4400 50 KVA PHYSICAL DIMENSIONS 1 2 ...
Страница 118: ...108 4400 Series Installation and Operation Manual 64527 008 FIGURE A 4 4400 50 KVA PHYSICAL DIMENSIONS 2 2 ...
Страница 119: ...109 4400 Series Installation and Operation Manual 64527 008 FIGURE A 5 4400 80 KVA PHYSICAL DIMENSIONS ...
Страница 120: ...110 4400 Series Installation and Operation Manual 64527 008 FIGURE A 6 4400 100 KVA PHYSICAL DIMENSIONS ...
Страница 136: ...This page left intentionally blank ...
Страница 137: ......