TopCold Romeo Скачать руководство пользователя страница 15

 18 

 

On and off 

Switching the instrument ON: press UP for more than 3 s (when pressing the button, the display shows ON). 

Switching the instrument OFF: press UP for more than 3 s. The display shows the message “OFF”, alternating with the 

temperature measured by the set probe. 

 

In off status, the following functions are disabled (if featured by the model): 



compressor control / duty setting / continuous cycle; 



defrost; 



fan control; 



alarms : ‘LO’, ‘HI’, ‘IA’, ‘cht’, ‘CHT’; 



door switch (A4= 7/8 ); 



buzzer (when available) 

 

While the following are enabled: 



temperature display, alternating with the message “OFF”; 



parameter display and setting; 



alarms: “E0”, “E1”, “E2”; 



the internal timer relating to parameter ‘dI’ is updated. If ‘dI’ expires in 



OFF status, a defrost is performed when restarting; 



auxiliary relay management, only in the following configurations: 



H1= = 1/2 (“E0” alarm only) 



H1= 3, A4= 6; 

 

Set point setting (desired temperature value) 

The easy and easy compact devices control the desired temperature (set point) inside the cabinet or cold room di-

rectly and dynamically. 

To view and modify the set point: 



press SET for 1 s, the set value will start flashing; 



increase or decrease the value using UP or DOWN; 



press SET to confirm the new value. 

 

Important

: the PJEZM* models fitted with keypad simply monitor the deviation from the set point and where neces-

sary signal na alarm. On these models, the set point can only be modified using parameter “St”. 

 

Manual defrost 

Not available on the easy and easy compact thermometer models (M). 

Press DOWN for more than 3 s (activated only if the temperature conditions are right. 

 15 

6. C

o

mmands 

ADJUSTING CAREL PJEZ

 

INTRODUCTION

 

Easy and easy compact are electronic microprocessor controllers with LED display, developed for the management of refriger-

a ng units, display cabinets and showcases. They exploit the experience and the success of the previous PJ32 range, with the 

objec ve of o

ering a product that is simpler and more economical.  

The structure of the parameters has been enhanced with new func ons for more dynamic and e

ec ve management of the 

temperature control and defrost. easy compact the smallest, most economical easy model, with one relay only, and a simpli

fi

ed 

display. 

Main characteris

Ɵ

cs 

The following table lists the main features of the easy and easy compact controllers. 

USER INTERFACE AND START UP 

Содержание Romeo

Страница 1: ...or safe and correct use of the equipment be sure to read the Safety Information in this manual before using it Manual Manual MAINTENANCE COMMANDS RECYCLING ANOMALIES UNPACKING ASSEMBLY PROCESURES OPERATION BASIC SECURITY PRECAUTIONS ...

Страница 2: ...2 31 ...

Страница 3: ...our Customer Service Department at 351 255 490 541 IMPORTANT INFORMATION PLEASE READ Please read these instructions carefully before installing or using If recommended procedure are not followed warranty claims will be denied Frilixa reserves the right to change specifications and product design without notice Such revisions do not entitle the buyer to corresponding changes improvements additions ...

Страница 4: ...vice away from walls Controller failed Probe unwired from the terminals Probe with cut wire Probe with humidity See if there is any message error on the dis play Check that switches are well connected if so call the technician to check for the possible failure Controller burnt Power excess Starts exceed Water in the circuit Replace the controller and check the origin of the failure Controller with...

Страница 5: ...replace it has to consider Refrigerant recovery if still existing Do not pour the oil of the replaced compressor To be quick in the replacement so that the oil of the new compressor is not in contact a too long time with the air as this later is highly hygroscope capacity of absorbing water Once the circuit is sealed make a good vacuum and recharge the quantity of refrigerant Filters should be als...

Страница 6: ...le damages to the equipment caused by moving objects such as trolleys cleaning machines forklifts and other equipment 4 Clean the interior and exterior of the cabinet with a smooth cloth and warm wa ter with neutral soap 5 of the water volume Avoid that is gets splashed by the cleaning products used to wash the establish ment The substances used in cleaning of the floors can attack chemically the ...

Страница 7: ...binet will be installed is according to what is indicated on the identification plate The connection must have a ground wire element that besides being necessary is demanded by law The appliance is not equipped with electric protection devices against overload so it is recommend to verify the electric safety level of the installation network where the cabinet will be installed Do not connect any o...

Страница 8: ...perature of the food products there placed Food products with temperature above the one recommend for the working of the equipment must not be placed inside the unit Do not leave the food products in boxes or pallets more than the necessary time to load the equip ment unit In the food display equipment food products must be removed during the night and placed in a Cold Room or similar equipment to...

Страница 9: ...dance with local electrical codes Ground wire separately shall be provided for all installations The properly connected equipment goes ensure proper operation Requirements for electrical feeding equipment are in the serial data plaque See Fig1 Fig1 Subtitles Recommended is a hotline properly protected size appropriate from the facility s main source of equipment To ensure the correct voltage to be...

Страница 10: ...emperatures food may be loaded For opti mum energy efficiency we recommend allowing a 1 1 2 clearance between the interior cabinet wall and product load Important Notices Do not spill water on the equipment or on electrical components Do not use pressure water jet or any type of metallic objects in order to remove impurities or dirt Do not use substances or materials that are abrasive or solvents ...

Страница 11: ... DOWN button respectively press SET to temporarily save the new value and display the parameter again repeat the procedure for any other parameters that need to be modified press the SET button for more than 3 s to permanently save the parameters and exit the parameter setting proce dure Setting the default parameters To reset the default parameters disconnect power from the instrument 11 4 Unpack...

Страница 12: ...eaching the end defrost set point check parameters dt dP and d4 check the efficiency of the defrost The message disappears when the next defrost ends correctly dF flashing defrost running this is not an alarm signal but rather a message that the instrument is running a defrost Only shown if d6 0 cht flashing dirty condenser pre alarm check parameters A4 Ac AE and Acd CHt flashing dirty condenser a...

Страница 13: ... least once a month The accumulation of ice in the evapora tor reduces the performance and makes the energy costs rise Never remove the ice from the evaporator with metal objects such as knifes or cutting objects When the evaporator has ice the ideal is to let it defrost naturally of the evaporator Water resulting from daily defrosting is collected in a plastic recipient that must be emptied whene...

Страница 14: ...els with 3 inputs and with multifunction input configured as a probe and after 1 s the temperature measured by the selected probe will be displayed To display the other probes press DOWN again To return to the normal display wait 3 s without pressing any buttons exit by timeout TABLES OF ALARMS AND PARAMETERS Table of alarms and signals When an alarm is activated the display shows the correspondin...

Страница 15: ...press SET for 1 s the set value will start flashing increase or decrease the value using UP or DOWN press SET to confirm the new value Important the PJEZM models fitted with keypad simply monitor the deviation from the set point and where neces sary signal na alarm On these models the set point can only be modified using parameter St Manual defrost Not available on the easy and easy compact thermo...

Страница 16: ...eted simply power up the controller to make it operative CAREL then recommends to check that the display does not show any alarm signals then set the time and date and finally set the parameters as desired The main parameters are as follows SC1 PROBE PS PASSWORD Functions available from the keypad ...

Отзывы: