 20 

The activation of the corresponding function is delayed by a timer, awaiting an external signal or disabled by 

another procedure that is already in progress. e.g. if is a continuous cycle in progress and a defrost is called, 

the latter will remain pending until the end of the continuous cycle, and the corresponding LED (defrost) will 

flash. 

E0 steady or flashing 

control probe error: 



probe not working: the probe signal is interrupted or short-circuited;



probe not compatible with the instrument;

The alarm signal E0 is steady if it is the only active alarm (the temperature value is not displayed), while it 

flashes if other alarms are active or the second probe is displayed. 

E1 flashing 

evaporator probe or food conservation probe error: 



probe not working, the probe signal is interrupted or short-circuited;



probe not compatible with the instrument;

E2 flashing 

condenser probe or food conservation probe error: 



probe not working, the probe signal is interrupted or short-circuited;



probe not compatible with the instrument;

IA flashing 

immediate or delayed alarm from multifunction digital input: 



check the multifunction input and parameters A4 and A7.

dOr flashing 

open door alarm: 



check the multifunction input and parameters A4 and A7.

LO flashing 

low temperature alarm. The probe has measured a temperature lower than the set point by a value that ex-

ceeds parameter AL: 



check parameters AL, Ad and A0.

The alarm is automatically reset when the temperature returns within the set limits (see parameter AL). 

HI flashing 

high temperature alarm. The probe has measured a temperature higher than the set point by a value that 

exceeds parameter AH. 

 13 

PERIODICAL MAINTENANCE

 

1.

The appliance,  when equipped with automatic defrosting programmer, should be switched off

and cleaned (see “Cleaning” chapter) at least once a month. 

The accumulation of ice in the evapora-

tor reduces the performance and makes the energy costs rise. Never remove the ice from the 

evaporator with metal objects such as knifes or cutting objects. When the evaporator has ice 

the ideal is to let it defrost naturally of the evaporator.

 

Water resulting from daily defrosting is collected in a plastic recipient that must be emptied, whenever 

necessary. In some models this procedure is not necessary since the water is re-evaporated in an ap-

propriate place. 

Special attention must be taken when a defrosting is made after ice is created in 

the evaporator, as the recipient for the condensed water may not have sufficient capacity and 

overflow.

 

2.

Before any maintenance or cleaning operation the appliance must be unplugged in order to guar-

antee, that it is not connected to electric power. The plug must be removed from the socket in order 

to insure that there is no electrical current of any type. Then remove all the products that are inside the 

cabinet and place them in a cold room or an adequate conservation place. 

Whenever necessary to remove any protection or isolation all the procedures for this must be correctly 

followed. Never restart functioning without making sure that all the removed elements have been dul-

ly fitted on the appliance. 

CLEANING

 

Internal and external cleaning must be done periodically with a soft cloth and warm water with neutral soap (5% of 

the water volume) without chlorine.  

In this chapter it is very important that the drainage hole of the condensed water is perfectly clear. 

“Dry carefully all the rests of water with the help of a sponge.” 

On the glass parts use appropriated liquid to clean them. 

Condenser cleaning should be made periodically or, whenever it shows impurities or filth that may hinder or block 

free circulation of air.  

The removal of impurities or filth must be done using a brush of soft hair (never use a metal brush), a vacuum cleaner 

or with air pressure flow. (View Fig2/3) 

Содержание Romeo

Страница 1: ...or safe and correct use of the equipment be sure to read the Safety Information in this manual before using it Manual Manual MAINTENANCE COMMANDS RECYCLING ANOMALIES UNPACKING ASSEMBLY PROCESURES OPERATION BASIC SECURITY PRECAUTIONS ...

Страница 2: ...2 31 ...

Страница 3: ...our Customer Service Department at 351 255 490 541 IMPORTANT INFORMATION PLEASE READ Please read these instructions carefully before installing or using If recommended procedure are not followed warranty claims will be denied Frilixa reserves the right to change specifications and product design without notice Such revisions do not entitle the buyer to corresponding changes improvements additions ...

Страница 4: ...vice away from walls Controller failed Probe unwired from the terminals Probe with cut wire Probe with humidity See if there is any message error on the dis play Check that switches are well connected if so call the technician to check for the possible failure Controller burnt Power excess Starts exceed Water in the circuit Replace the controller and check the origin of the failure Controller with...

Страница 5: ...replace it has to consider Refrigerant recovery if still existing Do not pour the oil of the replaced compressor To be quick in the replacement so that the oil of the new compressor is not in contact a too long time with the air as this later is highly hygroscope capacity of absorbing water Once the circuit is sealed make a good vacuum and recharge the quantity of refrigerant Filters should be als...

Страница 6: ...le damages to the equipment caused by moving objects such as trolleys cleaning machines forklifts and other equipment 4 Clean the interior and exterior of the cabinet with a smooth cloth and warm wa ter with neutral soap 5 of the water volume Avoid that is gets splashed by the cleaning products used to wash the establish ment The substances used in cleaning of the floors can attack chemically the ...

Страница 7: ...binet will be installed is according to what is indicated on the identification plate The connection must have a ground wire element that besides being necessary is demanded by law The appliance is not equipped with electric protection devices against overload so it is recommend to verify the electric safety level of the installation network where the cabinet will be installed Do not connect any o...

Страница 8: ...perature of the food products there placed Food products with temperature above the one recommend for the working of the equipment must not be placed inside the unit Do not leave the food products in boxes or pallets more than the necessary time to load the equip ment unit In the food display equipment food products must be removed during the night and placed in a Cold Room or similar equipment to...

Страница 9: ...dance with local electrical codes Ground wire separately shall be provided for all installations The properly connected equipment goes ensure proper operation Requirements for electrical feeding equipment are in the serial data plaque See Fig1 Fig1 Subtitles Recommended is a hotline properly protected size appropriate from the facility s main source of equipment To ensure the correct voltage to be...

Страница 10: ...emperatures food may be loaded For opti mum energy efficiency we recommend allowing a 1 1 2 clearance between the interior cabinet wall and product load Important Notices Do not spill water on the equipment or on electrical components Do not use pressure water jet or any type of metallic objects in order to remove impurities or dirt Do not use substances or materials that are abrasive or solvents ...

Страница 11: ... DOWN button respectively press SET to temporarily save the new value and display the parameter again repeat the procedure for any other parameters that need to be modified press the SET button for more than 3 s to permanently save the parameters and exit the parameter setting proce dure Setting the default parameters To reset the default parameters disconnect power from the instrument 11 4 Unpack...

Страница 12: ...eaching the end defrost set point check parameters dt dP and d4 check the efficiency of the defrost The message disappears when the next defrost ends correctly dF flashing defrost running this is not an alarm signal but rather a message that the instrument is running a defrost Only shown if d6 0 cht flashing dirty condenser pre alarm check parameters A4 Ac AE and Acd CHt flashing dirty condenser a...

Страница 13: ... least once a month The accumulation of ice in the evapora tor reduces the performance and makes the energy costs rise Never remove the ice from the evaporator with metal objects such as knifes or cutting objects When the evaporator has ice the ideal is to let it defrost naturally of the evaporator Water resulting from daily defrosting is collected in a plastic recipient that must be emptied whene...

Страница 14: ...els with 3 inputs and with multifunction input configured as a probe and after 1 s the temperature measured by the selected probe will be displayed To display the other probes press DOWN again To return to the normal display wait 3 s without pressing any buttons exit by timeout TABLES OF ALARMS AND PARAMETERS Table of alarms and signals When an alarm is activated the display shows the correspondin...

Страница 15: ...press SET for 1 s the set value will start flashing increase or decrease the value using UP or DOWN press SET to confirm the new value Important the PJEZM models fitted with keypad simply monitor the deviation from the set point and where neces sary signal na alarm On these models the set point can only be modified using parameter St Manual defrost Not available on the easy and easy compact thermo...

Страница 16: ...eted simply power up the controller to make it operative CAREL then recommends to check that the display does not show any alarm signals then set the time and date and finally set the parameters as desired The main parameters are as follows SC1 PROBE PS PASSWORD Functions available from the keypad ...

Отзывы: