background image

12  

 

Low leak intake dampers to prevent cold air from settling in the equipment during 
the off cycle. 

 

Low temperature safety stat(s) to force the equipment to a “safe” condition if the 
temperature  downstream  of  the  first  coil  drops  below  a  set  point  for  a  given 
amount  of  time.    This  safe  condition  typically  involves  shutting  down  the  airflow 
and opening the modulating valves.  If the valve control is provided by others and 
Titan  Air  supplies  a  freezestat,  only  the  blower  function  will  be  limited  by  our 
freezestat.  The field installer must ensure that the valve opens on loss of power, 
opens when the freezestat is tripped, and opens when needed during the off cycle 
to keep the cabinet warm enough to prevent freeze-up. 

DISCHARGE TEMPERATURE SENSOR BULB INSTALLATION & WIRING 

The  installing  contractor  may  be  responsible  for  field  installation  of  the  discharge  temperature 

sensor.    Install  discharge  temp  sensor  at  least  five  duct  diameters  away  from  the  equipment 
discharge to provide ample mixing of tempered air.  Field installation of the discharge temperature 
sensor  in  the  discharge  ductwork  results  in  a  better  measurement  of  the  average  supply  air 
temperature.  

Utilize shielded cable for field installed discharge sensor wiring

FIELD WIRING 

Most equipment will require field wiring.  Typically, field wiring is limited to power supply wiring, 

remote panel wiring, and intake or discharge damper wiring.  Occasionally, additional sensor wiring 
may be required. 

Carefully review the schematic and associated schematic symbol legend.  Note that legend may 

be on the parts/legend sheet rather than on the schematic. 

If an intake or discharge damper was ordered as a loose accessory, it will have to be mounted 

as  specified  in  the  Damper  Installation  Instructions  found  on  page  22  and  the  actuator  must  be 
wired.    The  remote  panel  must  be  mounted  in  a  convenient  location  and  wired  to  the  equipment.  
Interlocks between the exhaust, equipment and possibly spray booth will have to be connected by 
field wiring. 

  Low voltage wiring (terminals 100+) must be run in separate conduit or in shielded cables to 

prevent noise from affecting the control signals.  Additionally, good practice calls for all DC voltage 
(sensor and control signals) to be shielded or run separate from 24 VAC control wiring. 

  Typically, remote control panel wiring will sourced from a listed Class 2 transformer.  Therefore, 

most installations can take advantage of the opportunity to utilize less expensive wiring methods 
documented in NEC Article 725. 

  Communication wiring (for DDC control systems) should be wired per DDC manufacturer’s 

recommendations. 

 

NOTE:  All field wiring must conform to N.E.C. and/or any state or local codes. 

 

POST INSTALLATION 

Most of the equipment will likely be under a negative pressure when the blower is operating.  Dirt 

and  moisture  can  be  drawn  into  the  equipment.    Check  for  water  in  outdoor  equipment  after 
operation during a rain shower.

 

Sealing integrity should be rechecked on a yearly basis. 

 

NOTICE: Water damaged parts are not covered by Titan Air’s warranty  

 

Содержание TA-109

Страница 1: ......

Страница 2: ......

Страница 3: ...void in event the product is improperly installed and or operated under conditions other than normal published ratings improperly maintained misused or not in compliance with applicable codes or not...

Страница 4: ...rvation and are not intended to supplant requirements of federal state or local codes having jurisdiction These codes should be reviewed before installation of equipment All equipment must be installe...

Страница 5: ...8 BLOWER WHEEL 28 PLATE FINNED COIL CLEANING 29 CONDENSATE TRAP 29 GENERAL START UP INFORMATION 30 SPECIFIC EQUIPMENT DETAILS pages not numbered EQUIPMENT SPECIFICATION EQUIPMENT DRAWING SEQUENCE OF O...

Страница 6: ...ondensation Also check for damage caused by rodents and be sure to eliminate any dust that may have built up on the components while the equipment was in storage LONG TERM STORAGE Please observe the f...

Страница 7: ...otor sheave However some equipment may still utilize a variable pitch motor sheave on motors up to 30 Hp INDIRECT FIRED HEATING BURNER INFORMATION Titan Air Handlers can be equipped with inshot style...

Страница 8: ...es Gas piping and exhaust venting must be sized and installed to comply with applicable codes and standards If in doubt regarding the application of the heater contact a sales representative or the fa...

Страница 9: ...side of the equipment Review the equipment submittal drawing for the correct direction of the coil pull CURBING OUTDOOR MOUNTING The use of a full perimeter curb or mounting rails under the heater is...

Страница 10: ...of the blower A properly designed duct transition from the blower outlet to a larger duct is recommended for long ducts or ducts with numerous elbows The equipment was designed for a specific CFM and...

Страница 11: ...r coil piping is typically arranged to provide counterflow operation supply piping on lower air leaving side of coil and return on upper air entering side See Diagram on the right Verify that equipmen...

Страница 12: ...itional sensor wiring may be required Carefully review the schematic and associated schematic symbol legend Note that legend may be on the parts legend sheet rather than on the schematic If an intake...

Страница 13: ...g Options Recommended option for supporting accessories on a flat roof Other method of installation using sheet metal support legs IMPORTANT Not recommended for any unit larger than 125 model Typical...

Страница 14: ...be found packaged in either a clear plastic bag or corrugated box NOTICE There may be more than one package of assembly materials provided 1 Apply provided caulk tape to the face of the joint to be bo...

Страница 15: ...ed together caulk the external section seam s to provide a water tight seal IMPORTANT Check all external sheet metal seams for caulk shrinkage and re caulk if necessary Titan Air Inc does not warranty...

Страница 16: ...washers Check all sections of the unit thoroughly for assembly hardware The assembly hardware will be found packaged in either a clear plastic bag or corrugated box NOTICE There may be more than one p...

Страница 17: ...ction letter on the service side of the unit with the corresponding letter on the other section In addition also refer to the unit submittal drawing for proper assembly order 4 Lift blower section and...

Страница 18: ...TANT Re caulk unit lifting lugs after assembly Check all external sheet metal seams for caulk shrinkage and re caulk if necessary Titan Air Inc does not warranty water damage equipment Unit seam seali...

Страница 19: ...entry of snow rain and include an intake screen to meet ANSI standards Accessories on large equipment may be shipped in two pieces for field assembly As a result two damper actuators may need to be f...

Страница 20: ...h the hood to the filter section except in step five substitute inch bolts in for self taping screws to attach the hood to the filter section 7 After all of the accessories are installed caulk each se...

Страница 21: ...Titan Air highly recommends the discharge damper be mounted so the blades are orientated vertically If possible IMPORTANT Titan Air also highly recommends the discharge damper be mounted at the wall o...

Страница 22: ...d diffuser is supplied by others Support diffuser at two points using field supplied materials See example below Square Tubing DISCHARGE DAMPER Secure turning vanes once adjusted in the field by other...

Страница 23: ...t determine whether the drain pan is under negative or positive pressure DESIGN CONSIDERATION Calculate static pressure at the drain pan for worst case scenario Refer to the diagrams on the next page...

Страница 24: ...1 inch wg B A 5 C A B Pipe Diameter inches Insulation if applicable POSITIVE PRESSURE P TRAP CALCULATIONS D Minimum 1 2 inch E 1 2 inch Maximum Total Static Pressure F D E Pipe Diameter inches Insulat...

Страница 25: ...rocedure once per year FILTERS Dirty or clogged filters will restrict air flow which in turn affects the equipment performance Therefore it is necessary to check filters on a regular basis Several sta...

Страница 26: ...alignment and belt tension are critical to belt and bearing service life Incorrect belt tension or misalignment of sheaves can cause any of the following Premature failure of bearings Premature failur...

Страница 27: ...aves and then re tighten If a face width variation exists measure the difference between each side of the narrowest sheave and adjust until both sides are an equal distance from the straight edge BELT...

Страница 28: ...ns of dirt or moisture lubrication may be required every 6 months to 1 year Refer to website for specific manufacturer cut sheets pertaining to motor bearing maintenance Typical motor bearing lubricat...

Страница 29: ...ll also provide an initial check for pinholes or cracks that may not be visible Refrigerant leak detectors should be utilized for DX coils NOTICE Corrosion or deposits on copper or brazed joints may i...

Страница 30: ...eration per the sequence of operation must be verified Apparent malfunction of a component may be caused by improper supply conditions field wiring errors or other problems unrelated to the component...

Отзывы: