Operating Instructions
72
Setting Hour Meter Thresholds and
Resetting Hour Meters
The Hour Meter Threshold feature sets the
controller to alert the user that the unit has
operated for a defined number of hours. The
number of operating hours are entered in the
controller in the Hour Meter Threshold display.
The controller then generates a message when the
hour meter reaches the threshold setting.
NOTE: If the user does not desire to use the
Hour Meter Threshold feature to measure
maintenance intervals, etc., leave the settings at
“00000” to avoid nuisance messages.
The readings for Run Hours, Run Hours 50 Hz,
and Run Hours 60 Hz can be adjusted.
To set the HM1 Threshold or the HM2 Threshold,
or to reset Run Hours, Run Hours 50 Hz, or Run
Hours 60 Hz, complete the following steps.
1. Place the On/Off switch in the “ON” position.
2. Press the
E
NTER
key or the
E
SCAPE
key to enter
the Main Menu, if necessary.
3. Press the
U
P
or
D
OWN
key to scroll up or down
through the Main Menu to the Configuration
Menu.
4. Press the
E
NTER
key to enter the Configuration
Menu.
5. The Configuration Menu will be displayed.
with the cursor on LOP Restart.
6. Press the
U
P
or
D
OWN
key to scroll up or down
through the Configuration Menu to HM1
Threshold, HM2 Threshold, Run Hours, Run
Hours 50 Hz, or Run Hours 60 Hz.
7. Press the
E
NTER
key to display the Password
screen.
8. Enter the password, which is 0007. To enter
the password press the
E
NTER
key to move the
cursor to the last value and press the
U
P
or
D
OWN
key to scroll the value to 7. Press the
E
SCAPE
key and the
E
NTER
key at the same time
to enter the password.
9. The cursor will be under the H of the HM1 or
HM2 Threshold selection, or under the R of
the Run Hours, Run Hours 50 Hz or Run
Hours 60 Hz selection.
10. Press the
E
NTER
key to move the cursor to
select the value you want to change.
NOTE: For example, to change the setting
for the HM1 Threshold to 400 hours, press
the
E
NTER
key until the cursor is under the
third digit from the right. Then press the
U
P
key until that value reads 4.
11. Press the
U
P
or
D
OWN
key to scroll the selected
value up or down to the new setting.
12. Repeat steps 10 and 11 until you have changed
all the values to the new settings.
13. Press the
E
SCAPE
key and the
E
NTER
key at the
same time to save the new settings and return
to the Configuration Menu.
NOTE: Press the
E
SCAPE
key to return to the
Configuration Menu without saving the new
settings.
Содержание SGCO 3000
Страница 4: ......
Страница 12: ...SGCO 3000 Genset Addendum 12...
Страница 14: ...Genset Model Features 14...
Страница 22: ...Service Guide 22...
Страница 32: ...Unit Description Features Options 32...
Страница 78: ...Operating Instructions 78...
Страница 86: ...Electrical Maintenance 86...
Страница 114: ...Engine Maintenance 114...
Страница 124: ...Alternator Operation and Diagnosis 124...
Страница 130: ...Structural Accessory Maintenance 130...
Страница 138: ...Index 138...
Страница 140: ...Electrical and SG Menu Flow Diagrams 140...
Страница 141: ...141 SGCO 3000 Wiring Diagram Page 1 of 1...
Страница 142: ...142 SGCO 3000 Schematic Diagram Page 1 of 1...