Operating Instructions
69
Configuration Menu
The Configuration Menu is used to configure the
following controller functions (also see the
flowcharts on the following pages):
NOTE: The Configuration Menu requires that a
password (0007) be used change a setting. See
“Setting Hour Meter Thresholds and Resetting
Hour Meters” on page 72 for an example of how
change a setting.
•
LOP (Low Oil Pressure) Restart – The default
setting is OFF.
•
DEL (Delayed) Coldstart – The default setting
is ON. When this is set to ON, the controller
will delay energizing the exciter field until the
Water Temperature reaches 32 C (90 F).
•
HM1 (Hour Meter 1) Threshold – The default
setting is 0. When this is set to anything other
than 0, it sets the threshold that generates the
message “113. HOUR METER 1 HAS
EXCEEDED THRESHOLD”.
•
HM2 (Hour Meter 2) Threshold – The default
setting is 0. When this is set to anything other
than 0, it sets the threshold that generates the
message “114. HOUR METER 2 HAS
EXCEEDED THRESHOLD”.
•
ENG (Engine) Off Hours – The default setting
is 0. When this is set to anything other than 0,
it sets the threshold that generates the alarm
“110. ENGINE STOPPED DUE TO USER
SETUP”.
•
Factory Reset – The default setting is OFF.
When this is set to ON, the controller will
reset all run timers to 0 when the unit is turned
Off and then back On.
•
APU Connected – The default setting is OFF.
This is not used.
•
Output Voltage – The default setting is 460.
The other selection is 230, which is used is the
alternator is configured for an output voltage
of 230 Vac.
•
Fuel Sensor – The default setting is OFF. This
is set to ON if the unit is equipped with a fuel
level sensor.
•
Fuel Level – The default setting is 0. Possible
settings are 1 to 400 gallons. This sets the
threshold that generates the alarm “115. FUEL
LEVEL LOW”.
•
Crank Restarts – The default setting is 3.
Possible settings are 0 to 15, and 0 equals
infinite. This sets the number of restart
attempts that are allowed.
•
Telematic – The default setting is OFF. This is
not used.
To enter the Configuration Menu complete the
following steps:
1. Place the On/Off switch in the “ON” position.
2. Press the
E
NTER
key or the
E
SCAPE
key to enter
the Main Menu, if necessary.
3. Press the
U
P
or
D
OWN
key to scroll up or down
through the Main Menu to the Configuration
Menu.
4. Press the
E
NTER
key to enter the Configuration
Menu.
5. See “Setting Hour Meter Thresholds” on page
73 for an example of how change a setting.
Содержание SGCO 3000
Страница 4: ......
Страница 12: ...SGCO 3000 Genset Addendum 12...
Страница 14: ...Genset Model Features 14...
Страница 22: ...Service Guide 22...
Страница 32: ...Unit Description Features Options 32...
Страница 78: ...Operating Instructions 78...
Страница 86: ...Electrical Maintenance 86...
Страница 114: ...Engine Maintenance 114...
Страница 124: ...Alternator Operation and Diagnosis 124...
Страница 130: ...Structural Accessory Maintenance 130...
Страница 138: ...Index 138...
Страница 140: ...Electrical and SG Menu Flow Diagrams 140...
Страница 141: ...141 SGCO 3000 Wiring Diagram Page 1 of 1...
Страница 142: ...142 SGCO 3000 Schematic Diagram Page 1 of 1...