PARLOUR 3000-MV
DIRECT VENT GAS HEATER
16
B.
Clearance to window or door that may be opened:
Canadian Installation: 6” minimum (15 cm) for
appliances
10,000 Btuh (3 kW); 12” (30 cm)
for appliances > 10,000 Btuh (3 kW) and
100,000 Btuh (30 kW), 36” (91 cm) for
appliances > 100,000 Btuh (30 kW)
U.S. Installation: 6” minimum (15 cm) for
appliances
10,000 Btuh (3 kW); 9” (23 cm) for
appliances > 10,000 Btuh (3 kW) and
50,000
Btuh (15 kW), 12” (30 cm) for appliances >
50,000 Btuh (15 kW)
C.
Clearance to permanently closed window:
Clearance in accordance with local installation
codes and the requirements of the gas supplier.
D.
Vertical clearance to ventilated soffit located
above the terminal with a horizontal distance of
2 feet (61 cm) from the center line of the
terminal: Clearance in accordance with local
installation codes and the requirements of the gas
supplier.
E.
Clearance to unventilated soffit: Clearance in
accordance with local installation codes and the
requirements of the gas supplier.
F.
Clearance to outside corner: Clearance in
accordance with local installation codes and the
requirements of the gas supplier.
G.
Clearance to inside corner: Clearance in
accordance with local installation codes and the
requirements of the gas supplier.
H.
Clearance to each side of center line extended
above meter/regulator assembly:
U.S. Installation: Clearance in accordance with
local installation codes and the requirements of
the gas supplier.
I.
Clearance to service regulator vent outlet:
U.S. Installation: Clearance in accordance with
local installation codes and the requirements of
the gas supplier.
J.
Clearance to non-mechanical air supply inlet to
building or the combustion air inlet to any other
appliance:
U.S. Installation: 6” minimum (15 cm) for
appliances
10,000 Btuh (3 kW); 9” (23 cm) for
appliances > 10,000 Btuh (3 kW) and
50,000
Btuh (15 kW), 12” (30 cm) for appliances >
50,000 Btuh (15 kW)
K.
Clearance to a mechanical air supply inlet:
U.S. Installation: 3’ (91 m) above if within 10’ (3
m) horizontally
L.
Clearance above paved sidewalk or paved
driveway located on public property:
U.S. Installation: Clearance in accordance with
local installation codes and the requirements of
the gas supplier
M.
Clearance under veranda, porch deck, or
balcony:
U.S. Installation: Clearance in accordance with
local installation codes and the requirements of
the gas supplier
Maximum horizontal run 4’ after 2’ vertical rise.
Mobile Home Installation
Direct Vent appliances installed in Mobile Homes
must be secured to the floor in a minimum of two
locations. Drill holes through the two back legs and
counter sink and secure with lag screws. Fill counter
sink holes with putty or furnace cement and paint.
Alcove
This heater may be installed in an alcove with the
following minimum dimensions:
Width:
50”
Height:
50”
Depth:
32”
Содержание PARLOUR 3000-MV
Страница 8: ...PARLOUR 3000 MV DIRECT VENT GAS HEATER 8 LABORATORY LISTING LABEL...
Страница 10: ...PARLOUR 3000 MV DIRECT VENT GAS HEATER 10 FIGURE 1 DIAGRAM OF DIMENSIONS...
Страница 15: ...PARLOUR 3000 MV DIRECT VENT GAS HEATER 15 FIGURE 4 VENT TERMINATION LOCATIONS...
Страница 18: ...PARLOUR 3000 MV DIRECT VENT GAS HEATER 18 FIGURE 5 DIAGRAM OF VENTING REQUIREMENTS...
Страница 23: ...PARLOUR 3000 MV DIRECT VENT GAS HEATER 23 FIGURE 8 DIAGRAM OF CONTROL COMPONENTS...
Страница 33: ...PARLOUR 3000 MV DIRECT VENT GAS HEATER 33 FIGURE 12 GAS VALVE AND PILOT ASSEMBLY...
Страница 34: ...PARLOUR 3000 MV DIRECT VENT GAS HEATER 34 APPENDIX A VERTICAL PIPE INSTALLATION AIR INTAKE RESTRICTOR DISKS...
Страница 35: ...PARLOUR 3000 MV DIRECT VENT GAS HEATER 35 APPENDIX B PARLOUR STOVE WITH BURNER...