Blinds and switch actuator RMG 8, blinds actuator JMG 4 
and switch actuator module RME 8 - EIB

 

theben

 

As of: Apr-06 (Subject to change without notice)

Page  5 of 36 

 

1.2  Areas of Application 

 
 
 
 

The RMG 8 EIB switch actuator and the RME 8 / RMX 4 switch actuators module are suited for the 

following applications (examples): 

 

 

 

Control of awnings, blinds, roller shutters as well as various sunshades and sight protection 
devices 

 

 

Control of dormer windows and ventilation flaps 

 

 

Shading, lighting and heating greenhouses and winter gardens 
 

 

Lighting buildings and staircases 

 

 

Delayed activation/deactivation of groups of lights 

 

 

Short or long pulses for end-of-break gongs, toilet flushing installations or ventilation systems 

 
 
 

1.3  Differences between RMG 8 and JMG 4 

 

 
As opposed to RMG 8, JMG 4 is a pure drive controller and not a switch actuator. 
 
The drive functions of the JMG 4 are completely identical to those of the RMG 8 but the switching 
capacity of 8 A of the JMG 4 is lower (refer to the chapter Technical Data). 
 
The two devices can be expanded with an RME 8 or RMX 4 module. 
 
The extension modules can always be parameterised as desired as a drive controller or as a switch 
actuator for light etc. 

 

 
 
 

Содержание 490 0 250

Страница 1: ...e RME 8 EIB theben As of Apr 06 Subject to change without notice Page 1 of 36 RMG 8 Switch Actuator RME 8 RMX 4 Switch Actuator Modules JMG 4 Blinds Actuator for JMG 4 refer to Chapter 1 3 JMG 4 490 0 250 RMG 8 490 0 251 RME 8 490 0 252 RMX 4 490 0 256 Key for JMG 4 RMG 8 907 0 304 ...

Страница 2: ...s Drive Controller 18 3 4 5 Channel X Y Parameterised for 2 Switching Outputs 20 4 Commissioning 22 4 1 Reaction without ETS Programming 22 4 2 ETS Programming without Mains Voltage 22 4 3 Standard Drive Application 22 4 4 Expert drive application 24 4 4 1 Determining the Exact Full Running Time Down 24 4 4 2 Determining the Slippage Compensation of the Drive Mechanisms 27 4 4 3 Feedback of the Dr...

Страница 3: ...ff operations delay times can be individually set As a pulsing function activation restricted by timeout As an automatic time switch for staircase lighting with cut out early warning after the preset time has elapsed the light is switched off temporarily for 0 25 s and then switched on again for 30s Several inhibit and control objects enable a remote control of the connected devices e g central ra...

Страница 4: ...ghting period can be extended by repeated actuation of the switch when a person has to clean the staircase etc Cut out early warning function in compliance with DIN 18015 2 Simple input of the execution times in the ETS Large scope of functions due to 47 objects Even with traditional drive mechanisms any desired position can be approached due to the slippage compensation Forced object all drives u...

Страница 5: ...greenhouses and winter gardens Lighting buildings and staircases Delayed activation deactivation of groups of lights Short or long pulses for end of break gongs toilet flushing installations or ventilation systems 1 3 Differences between RMG 8 and JMG 4 As opposed to RMG 8 JMG 4 is a pure drive controller and not a switch actuator The drive functions of the JMG 4 are completely identical to those ...

Страница 6: ...oltage and a separate A C power supply Connections 1 bus connection RMG 8 and JMG 4 only 1 power connection 4 channels 2 for the RMX 4 consisting of 2 relays each n o contact Protection rating IP 20 in compliance with DIN EN 60 529 Protection class II following proper installation Permissible ambient temperature 5 C to 45 C 5T45 Housing dimensions 45 x 105 x 60 mm 45x53 5x60mm RMX 4 v H W D Weight...

Страница 7: ... lamp 1400 W Power consumption of the halogen lamp 1400 W Conv tubular fluorescent lamps uncompensated compensated in series 19 x 40 W 13 x 58 W 8 x 100 W compensated in parallel 5 x 40 W 4 7 μF 3 x 58 W 7 0 μF 1 x 100 W 18 μF dual switch 6 x 2 x 58 W 4 x 2 x 100 W Fluorescent flashlights with ECG 4 x 58 W Tubular fluorescent lamps with ECG dual switch 2 x 2 x 58 W Mercury discharge lamps uncompen...

Страница 8: ...and switch actuator RMG 8 blinds actuator JMG 4 and switch actuator module RME 8 EIB theben As of Apr 06 Subject to change without notice Page 8 of 36 2 3 Connection Diagram Connecting the EIB Installation Bus ...

Страница 9: ...s used to define which channels are to be parameterised as drive controller and which are to be parameterised as switching channels Drive 1 to 4 to 8 Is displayed when the respective channel is parameterised as a drive controller Channel 1 1 1 2 4 1 4 2 8 1 8 2 Is displayed when the respective channel is parameterised as a switching channel IMPORTANT After downloading the application or after the ...

Страница 10: ... example 3 3 2 Overview 3 3 2 1 Channel Parameterised as a Drive Mechanism When the channel is parameterised as a drive mechanism you can select the type of element that is to be driven see the table below Selected type of driven element Object no Property Roller shutter textile sunshade Blinds Name Drive 1 up down Function up down Type 1 Bit 0 Reaction receive Name Drive 1 stop Drive 1 step stop ...

Страница 11: ...lse function ON OFF delay Name Channel 1 1 switch Channel 1 1 staircase time switch Channel 1 1 impulse Channel 1 1 switch Function ON OFF Start stop Delayed ON OFF Type 1 Bit 0 Reaction receive Name Channel 1 1 state Function Feedback Type 1 Bit 1 Reaction send Name Channel 1 2 switch Channel 1 2 staircase time switch Channel 1 2 impulse Channel 1 2 switch Function ON OFF Start stop Delayed ON OF...

Страница 12: ...se time has elapsed or when a 0 is sent to the object the relay switches off Channel 1 1 delayed ON OFF If a 1 is sent to the object the relay switches on after the parameterised period of delay If a 0 is sent the delay refers to the switch off time Special cases A 0 sent during the switch on delay period or a 1 sent during the switch off delay period interrupts the procedure Object 1 Name refer t...

Страница 13: ...s object 0 for channel 1 1 Object 3 Name refer to the overview Function Drive 1 slats Presetting of a specific slat turn value in Can be inhibited by the Auto comfort object see below Channel 1 2 state Same function as object 1 for channel 1 1 Object 4 Name refer to the overview Function Drive 1 auto comfort Sending a 1 to this object inhibits the functions Drive 1 height and Drive 1 slats This fu...

Страница 14: ...ard operating status is assumed In the case of a storm the wind sensor sends a 1 to the security object and the sunshade is immediately retracted to the parameterised safety position IMPORTANT A security object may be controlled by one device only Otherwise different commands may cancel each other Annotation Reading the security objects i e with read value function of ETS software If the security ...

Страница 15: ...e 0 forced obj inactive 1 up 0 down Object 45 Name refer to the overview Function Central permanent ON For controlling switching outputs Using this object all the switching channels parameterised accordingly can be controlled from one central point In this case for example all the lights on one floor with the highest priority can be switched on simultaneously by pressing one button refer to the ap...

Страница 16: ...vice keys are always enabled only enabled if theben key for JMG 4 RMG 8 item no 907 0 304 is plugged Key lock deactivated If the option only enabled if key is plugged is selected the device keyboard is locked and manual operation is possible only if a key is inserted in the interface on the front of the device Manual mode automatically cleared after 30 min permanent Function of the manual button o...

Страница 17: ...ors connected to the security objects send cyclically the cycle time i e the time interval between 2 telegrams must be entered here Recommendation The monitoring time of the actuator must be twice as long as the cycle time of the device to be monitored Example If the air speed meter sends to the security object 1 every 5 minutes set the monitoring time to 10 minutes Allocation of the 0 Position to...

Страница 18: ...lind The type of device that is to be driven Full running time down 50 10 000 x 0 1s Keyboard input 50 to 10 000 Enter the measured runtime in 10th of a second 10 1 s 100 10 s etc Full Slats turn 20 200 x 20 ms Keyboard input 20 to 200 Enter the measured turning time of the slats in steps of 20 ms 100 100 x 20 ms 2 s Step time for object step stop shutter 3 55 x 20 ms Keyboard input 3 to 55 Desire...

Страница 19: ...e driven element to the parameterised security position Dependence on object Drives central up down no yes Is this drive to react to the Drives central up down object Behaviour after BUS voltage loss upper end of travel lower end of travel unchanged After a bus failure with existing power supply the drive move the driven element to a preferred position e g open the roller shutter Behaviour after B...

Страница 20: ... defined status after a bus failure This is important for consumers e g that must not continue operation without control Behaviour after BUS recovery unchanged switch ON switch OFF trigger timer Similar to the previous row Important for consumers e g that must not start operating again without control Behaviour at mains voltage recovery without BUS voltage switch ON remain OFF restore previous rel...

Страница 21: ... of a time base and a factor refer to the description of the parameters for the staircase time switch Factor for impulse width 1 255 x Time base Keyboard input 1 to 255 The impulse width is equal to the time base multiplied by the factor Example Time base 10 s x factor 2 is 2 x 10 s 20 s Parameters for ON OFF delay Time base for ON and OFF delay 1 sec 10 sec 30 sec 1 min The two delay times ON and...

Страница 22: ...outputs for upward movements are active for approx 4 minutes 4 2 ETS Programming without Mains Voltage Basically you do not need a connection to the mains voltage to program the device using the ETS The new parameters however come into force only after bus as well as mains voltage was jointly present at least once 4 3 Standard Drive Application Enter the running time in the ETS with some reserve s...

Страница 23: ...blinds until the slats no longer turn Start the slat turn with the telegram Slat with 100 FF hex The upward travel must end simultaneously with the slat turning motion Check 1 The slats do not turn when the next Up command is issued Check 2 Raise the blinds until the slats no longer turn Start the slat turn with the telegram Slat with 0 00 hex The downward travel must end simultaneously with the s...

Страница 24: ...he button on the device object 0 value 1 or object 2 value 100 3 Perform a complete raising operation until the Up LED on the controller is off using the button on the device object 0 value 0 or object 2 value 0 4 Perform a complete lowering operation until the Down LED on the controller is off using the button on the device object 0 value 1 or object 2 value 100 If the distance from the lower end...

Страница 25: ... is substantial increase the running time considerably Reload the application and repeat the procedure as of item 3 8 2 If the drive performs a stepwise lowering operation with further down commands steps of 100 ms extend the running time accordingly Reload the application and repeat the procedure as of item 3 8 3 The setting is valid if the end of travel has been reached or has been only slightly...

Страница 26: ...es of the drive mechanism and thus prevents precise positioning to a predefined position from either direction The slippage compensation eliminates this difference to a large extent Automatic execution of object value Slats after object Height enabled disabled for measuring the slippage Selection as to whether the height adjustment is to be restored to the slats position according to the Slats obj...

Страница 27: ...rive mechanism travel to the top position until the LED on the actuator goes out Lower the drive mechanism to the 20 position using the Height object Mark the position reached or measure the height Have the drive mechanism travel to the 80 position using the Height object Have the drive mechanism travel repeatedly between the 20 and the 80 positions using the Height object Finally set the drive me...

Страница 28: ...MG 4 and switch actuator module RME 8 EIB theben As of Apr 06 Subject to change without notice Page 28 of 36 Slippage 4 8 100 200 3 0 8 Annotation The mechanical properties of blinds may change due to ageing thus requiring an adjustment of the settings ...

Страница 29: ...ess click on the Set sending button and activate the Transmit checkbox confirm your input The same procedure can be used for the Slats object Example Address 02 0 051 Control of the drive mechanism height for several drive mechanisms Address 02 0 052 Feedback of the position of drive 4 IMPORTANT A feedback address must never be connected to another actuator input Annotation A noticeable deviation ...

Страница 30: ...yboard is locked or a priority is active Also refer to the appendices Priority Order of the Switching Output Controller of the Drive Controller 5 2 Manual Mode The manual mode is selected by pressing the manual key on the device The conditions for exiting this mode can be parameterised refer to Table 1 1 Parameters on the General tab 5 2 1 Manual Mode for Drive Channels In this mode the drives can...

Страница 31: ...eration without EIB voltage The actuator stores the position of the driven element after each stop This enables precise travelling to a new position from any other position To be able to perform the store the position correctly bus voltage and the application program must be present If the position of the drive is manually changed during a bus voltage failure any deviation will be compensated at t...

Страница 32: ...nge without notice Page 32 of 36 6 Appendices 6 1 Priority Order of the Drive Controller 1 and is stored in the case of a mains voltage failure 2 If ETS parameter Security is selected accordingly 3 If the associated Auto comfort object 0 is active 4 If the ETS parameter Dependence on object drives central up down is set to yes ...

Страница 33: ...ut Controller ON OFF Standard mode 1 If the ETS parameter Dependence on object Central permanent ON is set to yes 2 If the ETS parameter Dependence on object Central permanent OFF is set to yes 3 If the ETS parameter Dependence on object inhibit channels X X is set to yes 4 Relay statuses are retained or already issued commands are executed or replaced with the ETS settings for bus voltage failure...

Страница 34: ...ains Bus ON ON B C C PRG D D E D A Case Designation active parameter or reaction A Bus voltage recovery and failure without mains voltage No reaction relay is always off B Mains voltage recovery without bus voltage Behaviour at mains voltage recovery without bus voltage C Bus voltage recovery Behaviour after bus voltage recovery D Bus voltage failure Behaviour after bus voltage loss PRG Programmin...

Страница 35: ...as parameterised but is either defective or not available No EIB connection no bus voltage Power LED flashes ETS application not loaded or device is being programmed Communication problems with the ETS 1 Disconnect the EIB from the actuator 2 Press the programming button and keep it depressed 3 Connect the EIB again 4 As soon as the programming LED lights up the button can be released again Manual...

Страница 36: ...1 1 Central permanent OFF Feedback C1 1 OFF Dependence on object Inhibit Dependence Staircase time switch s 30 s vorwarnen Dependence Inhibit object C1 1 C1 2 Central permanent ON S tandard On Off staircase time switch impulse ON OFFdelay Impulse On Off delay OFF ON State after BUS ON BUS OFF Main ON is retained until E changes E Standard On Off RMG8new ...