Blinds and switch actuator RMG 8, blinds actuator JMG 4
and switch actuator module RME 8 - EIB
theben
As of: Apr-06 (Subject to change without notice)
Page 12 of 36
3.3.3 Description
of the Objects
•
Object 0
Name
(refer to the overview)
Function
Drive 1 up/down
Raise roller shutter/blinds with "0" and lower them with "1"
Channel 1.1 switch
Switch on the relay with "1" and switch it off with "0"
Channel 1.1 staircase
time switch
Activate automatic staircase time switch with "1" and deactivate it with "0".
As soon as the parameterised time has elapsed or when a "0" is sent to the
object, the relay switches off after a cutout early warning.
cutout early warning: The relay switches off for ¼ of a second, switches on
again for 30 seconds and then switches off completely.
Channel 1.1 impulse
Activate the impulse with "1" and deactivate it with "0".
As soon as the parameterised pulse time has elapsed or when a "0" is sent to
the object, the relay switches off.
Channel 1.1 delayed
ON/OFF
If a "1" is sent to the object, the relay switches on after the parameterised
period of delay.
If a "0" is sent, the delay refers to the switch-off time.
Special cases:
A "0" sent during the switch-on delay period or a "1" sent during the switch-
off delay period interrupts the procedure.
•
Object 1
Name
(refer to the overview)
Function
Drive 1 stop
A "1" or a "0" sent to the object stops the raising or lowering operation.
Drive 1 step/stop
If the blind is moving, it will be stopped.
Otherwise, a short movement of the slats is performed (step mode).
The direction of the "step" is defined by sending either a "0" or a "1" to the
object.
Steps will not be performed after the maximum possible slat turn position has
been reached ("Full Slats turn" parameter).
Channel 1.1 state
Feedback of the current relay status, e.g. for building visualization.
Example: A delayed switch-on operation is started, the feedback object is set
when the relay is switched on following the elapsed delay period.