Blinds and switch actuator RMG 8, blinds actuator JMG 4
and switch actuator module RME 8 - EIB
theben
As of: Apr-06 (Subject to change without notice)
Page 34 of 36
Converting Percentages to Hexadecimal and Decimal Values
Percentage
0 %
10 % 20 % 30 %
40 %
50 %
60 %
70 %
80 % 90 %
100
%
Hexadecimal 00 1A 33 4D 66 80 99 B3 CC E6 FF
Decimal
00 26 51 77 102 128 153 179 204 230 255
All the values from hex 00 to FF (decimal 0 to 255) are valid.
6.3 Definition: Mains Voltage Recovery and Bus Voltage Failure
OFF
OFF
Mains
Bus
ON
ON
B
C
C
PRG
D
D
E
D
A
Case
Designation
active parameter or reaction
A Bus voltage recovery and failure without mains
voltage
No reaction, relay is always off
B Mains voltage recovery without bus voltage
Behaviour at mains voltage recovery
without bus voltage
C Bus voltage recovery
Behaviour after bus voltage recovery
D Bus voltage failure
Behaviour after bus voltage loss
PRG Programming with ETS: Corresponds to
bus voltage f bus voltage recovery
Behaviour after bus voltage loss
Behaviour after bus voltage recovery
E
Bus and mains voltage failure simultaneously
Behaviour after bus voltage recovery*
* if the parameter “unchanged” is selected, the relay will remain OFF.