Blinds and switch actuator RMG 8, blinds actuator JMG 4
and switch actuator module RME 8 - EIB
theben
As of: Apr-06 (Subject to change without notice)
Page 23 of 36
Determining the complete slat turn for blinds:
•
Set the parameters on the "Drives general" ETS tab as follows:
•
Lower the blinds until the slats no longer turn.
•
Start the slat turn with the telegram "Slat [%]" with 100 % (= FF hex). The upward travel must end
simultaneously with the slat turning motion.
•
Check 1
:
The slats do not turn when the next "Up" command is issued.
•
Check 2:
Raise the blinds until the slats no longer turn.
Start the slat turn with the telegram "Slat [%]" with 0 % (= 00 hex).
The downward travel must end simultaneously with the slat turning motion.
The slats do not turn when the next "Down" command is issued.