4 Commissioning
The ETS database can be found at www.theben.de/downloadseite.htm#g.
4.1 Reaction without ETS Programming
Without ETS programming, all the channels are set to the "drive" mode.
Immediately after the power supply has been switched on, the outputs for upward movements
are active for approx. 4 minutes.
4.2 ETS Programming without Mains Voltage
Basically, you do not need a connection to the mains voltage to program the device using the ETS.
The new parameters, however, come into force only after bus as well as mains voltage was jointly
present at least once.
4.3 Standard Drive Application
Enter the running time in the ETS with some reserve (stop-watch time + 20 %). Roller shutters in
particular require more time for travelling up than they do for travelling down.
Standard settings recommended for the Expert functions on the "Drives general" tab for blinds.