Blinds and switch actuator RMG 8, blinds actuator JMG 4
and switch actuator module RME 8 - EIB
theben
As of: Apr-06 (Subject to change without notice)
Page 18 of 36
3.4.3
Function of the Channels
Table 1-3: Parameters on the "Function of the channels" tab
Designation
Values
Description
Function of channel 1,
2, 3, 4 ... 8
Drive
2 switching outputs
Each channel can either be
parameterised as a drive controller
or as a controller for 2 switching
outputs.
IMPORTANT:
When changing the function of channels from switching channel to drive (or vice
versa), the device must be reset by interrupting the power supply (for at least 2 s).
3.4.4
Drive x (Channel as Drive Controller)
Table 1-4: Parameters on the "Drive 1, Drive 2 ... Drive 8" tab
Designation
Values
Description
Drive application
Shutter / awning
Blind
The type of device that is to be
driven.
Full running time
"down"
50 ... 10.000 [x 0.1s]
Keyboard input 50 to 10,000
Enter the measured runtime in 10
th
of a second.
10 = 1 s, 100 = 10 s etc.
Full Slats turn*
20 ... 200 [x 20 ms]
Keyboard input 20 to 200
Enter the measured turning time of
the slats in steps of 20 ms.
100 = 100 x 20 ms = 2 s
Step time for object
"step/stop shutter*
3 ... 55 [x 20 ms]
Keyboard input 3 to 55
Desired pulse length for step/stop
mode.
10 = 10 x 20 ms = 0.2 s
Position at security
begin / end
no reaction
upper end of travel / unchanged
upper end of travel / lower end of
travel
lower end of travel / unchanged
lower end of travel / upper end of
travel
Reaction of the driven element
when the "Security" status is
enabled and disabled.
In the case of the standard
application "upper end of travel /
unchanged" the drive moves the
driven element to the upper end of
travel as soon as the security status
is enabled (e.g. due to a storm) and
remains in this position when the
security status is disabled.