Remote Control
71
0x01 – Star, no neutral
0x02 – Star, With neutral
0x03 – Zig-zag, no neutral
0x04 – ZigZag, with neutral
0x05 – Single Phase (conventional transformer)
0x06 – Single Phase (current transformer)
0x0E – Use Range Extension transformer
The phase displacement is between 0 to 11.
<Voltage> (integer) indicates the voltage at which the transformer was tested.
It will be one of:
0x0A (10) - 10 Volts energization
0x28 (40) - 40 Volts energization
0x64 (100) - 100 Volts energization
<HVNomVolatge> (float) is the Voltage of the nominal tap on the HV Side.
<LVNomVolatge> (float) is the Voltage of the nominal tap on the LV Side.
<NumTaps> (integer) is the number of taps that have been defined for the
transformer.
<BotTap> (integer) is the index of the bottom tap of the transformer.
<NomTap> (integer) is the index of the nominal tap of the transformer.
<StepVal> (float) is the Tap-Tap step value, which is either in Volts or a
percentage of the
nominal tap voltage, based on the Step Unit set. . A negative step value indicates
that the
tap is on the HV side. A positive step value indicates that the tap in on the LV side.
A step value of zero indicates that the tap voltages should be set manually.
<MeasTap> (integer) indicates the number of taps that have actually been
measured. If a
test has been performed, and this parameter is 0, only a single winding has been
tested.
Comments:
None
Memory:Read:Info
This returns the test information for the specified
Structure:
+M:R:I:~:
Fields:
<MemNo> (integer) is the memory number to be read. This is in the range of 0 to
100.
Returns:
+OK: <Serial>:<Location>:<Type>:
<Operator>:<Deviation>:<TimeDate>:~: - Memory read OK
+ERROR:0903:~: - Memory has no data
+ERROR:0904:~: - Memory Corruption detected
+ERROR:0905:~: - Specified memory is out of range
<Serial> (string) is the 20 character unit serial number
<Location> (string) is the 20 character unit location code
<Type> (string) is the 20 character manufacturers type code
<Operator> (string) is the 20 character operator code
Содержание TTR 2795
Страница 1: ...Operating Instructions HAEFELY TEST AG TTR 2795 Transformer Turns Ratio Meter Version 1 4 ...
Страница 10: ...6 Introduction Maximum Roll Diameter Outer 50mm Inner 10mm ...
Страница 22: ...18 Connection and Setup Figure 11 Connecting to three phase BCT ...
Страница 101: ...Application Software APSW 2795 97 ...
Страница 111: ...Miscellaneous 107 14 7 Conformity ...