36
Setting Up Tests
LV Config
The LV configuration sets the winding configuration of the LV side of the
transformer. It is not displayed if the HV Configuration is set to “Auto 3 Ph” because
the system attempts to determine the LV winding automatically. It is not shown if the
HV configuration is set to “CT” or “Single” because there are no alternative
configuration possibilities. The options for the LV Configuration are
D
Y
Yn
Z
Zn
Ph Displacement
The Phase displacement is only displayed if a three-phase transformer
configuration has been set (both HV Config and LV Config have been set). It allows
the user to set the phase displacement of the transformer, or to select automatic
determination of the phase displacement. The phase displacement values set
depend on the HV and LV configuration of the transformer:
Configuration
Displacements
D-D, D-Z, D-Zn, Z-D, Zn-D, Y-Y, Y-Yn, Yn-Y, Yn-Yn
0-2-4-6-8-10
D-Y, D-Yn, Y-D, Y-Z, Y-Zn, Yn-D, Yn-Zn, Z-Y, Z-Yn, Zn-Y, Zn-Yn
1-3-5-7-9-11
Test Voltage
The test voltage allows the user to set the voltage applied to the transformer for the
test to be set. The options are:
Auto
1V
10V
40V
100V
In automatic mode, the voltage is set based no the current drawn by the
transformer. The system will use the highest voltage it can without overloading
itself.
HV Nom Voltage
The HV Nom Voltage is the boilerplate voltage for the high voltage winding of the
transformer. Where a transformer is tapped, it is the HV winding voltage for the
nominal (center) tap.
LV NomVoltage
The LV Nom Voltage is the boilerplate voltage for the low voltage winding of the
transformer. Where a transformer is tapped, it is the LV winding voltage for the
nominal (center) tap
Total Taps
The Total number of taps sets whether the transformer is tapped or not and the
number of taps on the transformer. If there are no taps on the transformer the
“Total Taps” should be set to one. If only the LV or HV winding is tapped, it should
be set to the number of taps plus one, i.e. the number of outputs. If the transformer
is tapped on both the HV and LV sides, then the “Total Taps” is set to the total
number of possible combinations. The maximum number of taps that can be set is
125.
Bot Tap Number
The bottom tap number sets the reference number for the lowest tap on the
transformer. All the other taps are referenced relative to this tap. The method of
referencing depends on whether Alphabetic or Numeric tap numbering is used. For
more information see the later section on setting up tapped transformer tests.
Nom Tap Number
This sets the reference number for the nominal tap on the transformer - this is the
tap that the “Nom HV Voltage” and “Nom LV Voltage” above refer to.
Tap Setup
This sets how the transformer is tapped respectively how the taps are entered. “HV”
for a tap changer on HV side, “LV” for taps on the Low Voltage LV side and
“Manual” to enter each tap (HV and LV) value manually when leaving this menu-
point. To change already manual entered tap values just re-set the tap setup as
“Manual”.
Step Tap-Tap
The Step Tap-Tap sets the change in output voltage between each tap. If tap
stepping is set as voltage in the options menu, it is set in terms of voltage steps,
otherwise it is set in terms of a percentage of nominal voltage.
Max Deviation
The Maximum % deviation sets the limit for how far the measured ratio for a tap is
allowed to differ from the theoretical value based on the nominal HV and LV
voltages. If the deviation exceeds this level then the system reports the transformer
as having failed the test. If the Max Deviation is set to zero, there is no checking of
winding deviation.
Содержание TTR 2795
Страница 1: ...Operating Instructions HAEFELY TEST AG TTR 2795 Transformer Turns Ratio Meter Version 1 4 ...
Страница 10: ...6 Introduction Maximum Roll Diameter Outer 50mm Inner 10mm ...
Страница 22: ...18 Connection and Setup Figure 11 Connecting to three phase BCT ...
Страница 101: ...Application Software APSW 2795 97 ...
Страница 111: ...Miscellaneous 107 14 7 Conformity ...