60
Remote Control
The instrument identification field is always returned as “TETTEX2795” irrespective
of the
instrument options, as these do not affect the operation of the system
<Serial No> is the serial number of the instrument. This is passed as a text string.
<Version> is the current software version. This is passed as a text string of the
form “Vx.xx”
Comments:
None
11.5
Test Control Functions
The test control functions allow the remote system to run a test on a connected transformer and to gather the results
from the unit under test. The user can set up a complete test profile over the remote link, or just set up the parts that
need to be updated for the current test. These functions all operate on the working memory, and do not affect the
main memory system.
The Test command has a number of sub-commands:
Setup
:
Setup the basic test parameters - this is the minimum set of parameters
required to perform a test.
Info
:
Setup the additional information for the test
Measure
:
Run/Monitor/Control the measurement sequence
Results
:
Review the gathered results for the test
Test:Setup:VectorGroup
This sets the vector group of the transformer to be tested
Structure:
+T:S:V:<VectorGroup>:<TestVoltage>:~:
Fields:
<VectorGroup> (integer) is the vector group of the transformer under test. This is an
integer value that determines the configuration of the transformer and the phase
displacement. Bits 15-12 determine the HV winding configuration, bits 11-8
determine the
LV winding configuration and bits 7-0 determine the phase displacement. The
possible
values for the winding configurations are:
0x00 – Delta
0x01 – Star, no neutral
0x02 – Star, with neutral
0x03 – Zig-zag, no neutral
0x04 – Zig-zag, with neutral
0x05 – Single Phase (conventional transformer)
0x06 – Single Phase (current transformer)
0x0E – Use Range Extension transformer
0x0F – Attempt to auto determine winding configuration.
The phase displacement is set at a value of 0 to 11, to indicate the actual
displacement of
the transformer. If it is set at 0xFF, the system will attempt to auto-determine the
phase
displacement.
Note: if the HV winding is set as single phase (conventional or current), use range
extension transformer or Attempt to auto determine winding configuration, the
setting for
the LV winding is ignored.
<TestVoltage> (integer) determines the voltage at which the transformer will be
tested.
If it is set as zero, or as an invalid value, the system will use automatic voltage
Содержание TTR 2795
Страница 1: ...Operating Instructions HAEFELY TEST AG TTR 2795 Transformer Turns Ratio Meter Version 1 4 ...
Страница 10: ...6 Introduction Maximum Roll Diameter Outer 50mm Inner 10mm ...
Страница 22: ...18 Connection and Setup Figure 11 Connecting to three phase BCT ...
Страница 101: ...Application Software APSW 2795 97 ...
Страница 111: ...Miscellaneous 107 14 7 Conformity ...