7. Survey of possible malfunctions and irregularities in operation
MALFUNCTION
CAUSE
ELIMINATION
- there is no voltage
on the control panel
at switching on
-
there is no power supply from the net
on one or more phases
-
fuse 2,5A on the control panel is
burned through
-
RCCB switch is disconnected
-
replace fuse 2,5A and check
the cause of burning
-
contact authorized service
personnel to resolve the
problem
- By switching on,
the switches on the
control panel display
the voltage, but the
boiler does not heat
-
check the adjustment of the room
thermostat,
-
limiting thermostat is activated
-
indicator of air presence in the boiler
blocked the operation,
-
defective switch,
-
operation thermostat is defective,
-
heaters are burned through
-
check the set temperature on
the room thermostat, replace
batteries, or the room
thermostat is faulty,
-
deaerate the boiler in order to
turn off the lamp “air in boiler”
- temperature in
boiler is on desired
value, but radiators
do not heat
-
circulation pump does not operate,
-
air stopper on central heating
installation prevents circulation
-
start mechanical pump
(CHAPTER 4.)
-
deaerate installation
-
boiler does not
provide enough
heat
-
one phase is missing on supply
-
in two-stage thermostats the second
stage is not functioning
-
the second or the third stage is not
manually turned on,
-
one switcher is defective,
-
a part of heater is burned through
-
in a three-phase system the three
different phases are not brought to the
boiler
-
check fuses on the main
panel,
-
contact authorized service
personnel to resolve the
problem
-
the switcher can
be heard while
operating (it
buzzes)
radio and TV-
interferences
-
poor voltage in the net
-
defective switcher
-
contact authorized service
personnel to resolve the
problem
-
when turning on
or off the
operation
thermostat,
radio and TV-
interferences
occur
-
defective operation thermostat,
-
defective blockade (RC – protection)
-
contact authorized service
personnel to resolve the
problem
-
boiler in
operation “roars”
-
the system is not well deaerated,
-
defective heater
-
deaerate the system
-
contact authorized service
personnel to resolve
problem
-
pressure in the
system varies
-
defective expansion vessel,
-
the vessel pressure is too low or too
high
-
contact authorized service
personnel to resolve the
problem
Page 37
Содержание TERMO-Blok
Страница 2: ...TMS UT 0114 T03 1 INSTRUCTIONS FOR USE We reserve the right of alternations ...
Страница 25: ...TMS UT 0114 T01 1 INSTRUCTIONS FOR INSTALLATION We reserve the right of alternations ...
Страница 66: ...TMS UT 0114 T01 1 Page 39 ...
Страница 76: ...Termostroj Croatia APPENDIX 3 Termo Blok PTV m 2 Electric sketch Termo Blok PTV m 3 Connection plate Page 49 ...
Страница 83: ...Termostroj Croatia APPENDIX 5 Termo Blok e 2 Electric sketch Termo Blok e 3 Connection plate Page 56 ...
Страница 86: ...Termostroj Croatia APPENDIX 6 Termo Extra e 2 Electric sketch Termo Extra e 3 Connection plate Page 59 ...
Страница 89: ...Termostroj Croatia APPENDIX 7 Termo Blok m 2 Electric sketch Termo Blok m 3 Connection plate Page 62 ...
Страница 92: ...Termostroj Croatia APPENDIX 8 Termo Extra m 2 Electric sketch Termo Extra m 3 Connection plate Page 65 ...