Wiring the Enclosure
Power Wiring
SAFETY NOTICE
All power wiring must be performed by a competent electrician, appropriately licensed in the jurisdiction where the installation
takes place. All electrical work must be done in full compliance with all electrical and safety norms applicable to the installation
site. Isolate all power feeds before opening the enclosure.
Tempest Lighting, Inc., its employees and agents will not be held responsible for damage or injury caused by disregarding this
notice.
Electrical Standards
Important:
Enclosure model numbers including .US are for use in countries using US and Japanese style electrical systems:
200-208VAC 50/60Hz
Enclosure model numbers including .IN are for use in countries using European style electrical systems:
220-250VAC 50/60Hz
Note:
(1)
Fans and Heaters are rated 200-250V
(2)
Electronics are autosensing for any voltage 90-265VAC, 50/60Hz
(3)
ActiveCool and AC Assist Coolers are 200-250VAC, but supplied in 50Hz and 60Hz versions
AC Supply Voltage
Tempest Cyclone enclosures require supply voltage in the nominal range 200-250VAC, 50/60Hz.
Tempest G4 enclosures are very tolerant of supply voltage variations:
•
DEC4 controller has a universal power supply and operates on 90-265VAC
•
Enclosure fans and heaters are rated 200-250VAC. Fans are over-dimensioned to cool adequately down to 200V, and
heaters compensate thermostatically by increasing duty cycle on lower supply voltages.