Cyclone User Manual
25
ActiveCool Control Settings
Remove the control cover, located below the return air ring:
Set your controller: The controller is factory set at 14°C (57°F) and
will be displaying the current cool air temperature.
To check or change these settings:
PRESS [SET]. C is displayed. Use
or
to toggle between
Celsius and Fahrenheit, the letter C or F is then displayed.
PRESS [SET] again, the current TARGET TEMPERATURE (set
point) is displayed. Use
or
to change the target cool air
temperature.
Note: For best results always set the unit to a
realistic temperature that it can maintain.
PRESS [SET] again. The number 1 is displayed, with the
message (DIF1). This is the temperature difference
(hysteresis) setting
–
DO NOT CHANGE.
PRESS [SET] again. Display shows C1 (cooling mode)
–
DO
NOT CHANGE.
(the alternate setting is H1, meaning heat
mode).
PRESS [SET] again. The display shows (d1), and 0. This is the
delay setting
–
DO NOT CHANGE.
PRESS [SET] again. The unit displays the current air
temperature at the cooler sensor. This is the default display
and the control will always reset to this display automatically.
This completes the “set” cycle routine.
Important: All sites are different! Check the projector intake air
temperature from the projector control system, and adjust the
ActiveCool cooler set point to find the optimum setting for your
installation.
In the event of a fault, the buzzer will sound, and the fault
indicator light will be lit.
Buzzer